| Plan Review Notes For Permit 12010311 |
| Permit Number |
12010311 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-19 13:33:41 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. REVISE EXPOSURE CATEGORY TO EXPOSURE C OR CONTACT ME | | | TO DISCUSS RATIONALE FOR EXPOSURE B. FBC1609, FBC | | | R301.2.1.4. NOTE THAT THE CODE (AND DEFINITIONS FOR | | | EXPOSURE B AND EXPOSURE C) CHANGED EFFECTIVE MARCH 1, | | | 2009. | | | | | | 2. FLOOR PLAN IS NOT LEGIBLE. CODE COMPLIANCE WITH | | | REQUIREMENTS SUCH AS ACCESSIBILITY, REQUIRED FIRE | | | RATING, PANIC DEVICES, ETC. CANNOT BE DETERMINED BASED | | | ON THE INFORMATION PROVIDED. PROVIDE A LEGIBLE FLOOR | | | PLAN AND PROVIDE ENOUGH INFORMATION TO DEMONSTRATE CODE | | | COMPLIANCE. | | | | | | 3. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR | | | THE DOOR PROPOSED. A NOA NUMBER IS PROVIDED ON THE PLAN | | | BUT THE PRODUCT APPROVAL IS TO BE PROVIDED FOR REVIEW. | | | | | | | | | | | | |
|