Plan Review Notes
Plan Review Notes For Permit 12010311
Permit Number 12010311
Review Stop B
Sequence Number 1
Notes
Date Text
2012-01-19 13:33:41****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. REVISE EXPOSURE CATEGORY TO EXPOSURE C OR CONTACT ME
 TO DISCUSS RATIONALE FOR EXPOSURE B. FBC1609, FBC
 R301.2.1.4. NOTE THAT THE CODE (AND DEFINITIONS FOR
 EXPOSURE B AND EXPOSURE C) CHANGED EFFECTIVE MARCH 1,
 2009.
  
 2. FLOOR PLAN IS NOT LEGIBLE. CODE COMPLIANCE WITH
 REQUIREMENTS SUCH AS ACCESSIBILITY, REQUIRED FIRE
 RATING, PANIC DEVICES, ETC. CANNOT BE DETERMINED BASED
 ON THE INFORMATION PROVIDED. PROVIDE A LEGIBLE FLOOR
 PLAN AND PROVIDE ENOUGH INFORMATION TO DEMONSTRATE CODE
 COMPLIANCE.
  
 3. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR
 THE DOOR PROPOSED. A NOA NUMBER IS PROVIDED ON THE PLAN
 BUT THE PRODUCT APPROVAL IS TO BE PROVIDED FOR REVIEW.
  
  
  
  