2012-01-24 13:19:38PLANS DENIED
 1) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS PER
 TABLE 403.3 2007 FBC (M) .
 2) REFER TO SECTION 13-409.AB.3.3 SHUT OFF DAMPER
 CONTROL 2007 ENERGY CODE.
 3) PROVIDE A DETAIL FROM A ENGINEER ON CONDENSER TO
 SLAB TIE DOWN.
 PER SECTION 301.12 WIND RESISTANCE 2007 FBC (M) .