| Plan Review Notes For Permit 12010285 |
| Permit Number |
12010285 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-24 13:19:38 | PLANS DENIED | | | 1) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS PER | | | TABLE 403.3 2007 FBC (M) . | | | 2) REFER TO SECTION 13-409.AB.3.3 SHUT OFF DAMPER | | | CONTROL 2007 ENERGY CODE. | | | 3) PROVIDE A DETAIL FROM A ENGINEER ON CONDENSER TO | | | SLAB TIE DOWN. | | | PER SECTION 301.12 WIND RESISTANCE 2007 FBC (M) . | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|