Plan Review Notes
Plan Review Notes For Permit 12010283
Permit Number 12010283
Review Stop P
Sequence Number 3
Notes
Date Text
2012-04-30 16:14:43THE COMMENTS FROM THE FIRST TWO REVIEWS HAVE NOT BEEN
 ADDRESSED. SEE BELOW.
  
 2007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE BATH ROOM FIXTURES ARE NOT PROPERLY VENTED. PER
 FBCR P3108.2.1, NOT MORE THAN ONE WET-VENTED FIXTURE
 DRAIN SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED
 FIXTURE DRAIN CONNECTION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]