2012-01-30 16:01:1612010283
 1805 FLORIDA AVE
 INTERIOR RENOVATION OF BACK COTTAGE
  
 INDICATE LOCATION OF THE ELECTRICAL SERVICE AND MAIN
 DISCONNECT. NEC 215.5
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. FBC R313
 INDICATE THAT ALL NEW RECEPTACLES WILL BE TAMPER
 RESISTANT. NEC 406.11
 ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE
 PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC
 210.12
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND NEC 250.94
 ADD RECEPTACLES SO THAT NO WALL SPACE IS MORE THAN 6
 FEET FROM A RECEPTACLE AND ALL WALL SPACES MORE THAN 2
 FEET IN WIDTH HAVE A RECEPTACLE I.E. KITCHEN. NEC
 210.52
 AT LEAST ONE GFCI PROTECTED RECEPTACLE IS REQUIRED
 OUTSIDE FRONT AND BACK. NEC 210.52
  
  