Plan Review Notes
Plan Review Notes For Permit 12010282
Permit Number 12010282
Review Stop B
Sequence Number 3
Notes
Date Text
2012-05-01 10:01:502007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 THE FOLLOWING ITEMS FROM THE FIRST TWO REVIEWS WERE NOT
 ADDRESSED:
  
 1) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORM. 2007 FBC ENERGY GLITCH AMENDMENTS
 N1100.2.2
  
 2) THE PRODUCT APPROVALS REQUIRED BY DCA RULE 9N-3 THAT
 WERE SUBMITTED FOR THE SH-600 AND SH-700 SINGLE HUNG
 WINDOWS AND THE FD-650 FRENCH DOORS HAVE INCOMPLETE
 INSTALLATION DRAWINGS. WHEN DOWNLOADING THEY HAVE TO BE
 SHRUNK TO FIT ON THE 8.5 " X 11" PAPER.
  
 3) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. CITY AMENDMENTS 106.3.3
  
 4) SHOW COMPLIANCE WITH FBCR 301.2.1.2 FOR IMPACT
 PROTECTION OF GLAZED OPENINGS. SUBMIT (2) TWO COPIES OF
 A PRODUCT APPROVAL FOR STORM PANELS, A KEY PLAN AND AN
 INSTALLATION SCHEDULE FOR THE STORM PANELS. THE WINDOW
 AND DOOR SCHEDULE INDICATES THAT THE FIRST FLOOR
 WINDOWS AND FRENCH DOORS ARE NOT IMPACT RATED AND
 REQUIRE SHUTTERS.
  
 5) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE RESPOND
 TO REVIEW COMMENTS IN WRITING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]