| Notes |
| Date |
Text |
| 2012-03-29 10:53:39 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY BUILDING | | | | | | THE FOLLOWING ITEMS FROM THE FIRST REVIEW WERE NOT | | | ADDRESSED: | | | | | | 2) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY | | | CALCULATION FORM. | | | | | | 9) SUBMIT TWO COMPLETE SETS OF PRODUCT APPROVALS FOR | | | THE EXTERIOR FRENCH DOORS AS REQUIRED BY DCA RULE 9N-3. | | | | | | 10) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE | | | SINGLE HUNG WINDOWS DO NOT MEET THE NEGATIVE COMPONENT | | | AND CLADDING PRESSURE OF - 47.2 PSF SPECIFIED ON PLAN | | | SHEET A-2. THE MAXIMUM DESIGN PRESSURE ON THE PRODUCT | | | APPROVAL IS +45 / -45 PSF. FBC R301.2.1 ALSO THE | | | INSTALLATION INSTRUCTIONS ARE INCOMPLETE. WHEN | | | DOWNLOADING THEY HAVE TO BE SHRUNK TO FIT ON 8.5 X 11 | | | PAPER. | | | | | | 11) SHOW COMPLIANCE WITH FBCR 301.2.1.2 FOR IMPACT | | | PROTECTION OF GLAZED OPENINGS. SUBMIT (2) TWO COPIES OF | | | A PRODUCT APPROVAL FOR STORM PANELS, A KEY PLAN AND AN | | | INSTALLATION SCHEDULE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|