2012-03-29 10:53:392007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 THE FOLLOWING ITEMS FROM THE FIRST REVIEW WERE NOT
 ADDRESSED:
  
 2) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORM.
  
 9) SUBMIT TWO COMPLETE SETS OF PRODUCT APPROVALS FOR
 THE EXTERIOR FRENCH DOORS AS REQUIRED BY DCA RULE 9N-3.
  
 10) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 SINGLE HUNG WINDOWS DO NOT MEET THE NEGATIVE COMPONENT
 AND CLADDING PRESSURE OF - 47.2 PSF SPECIFIED ON PLAN
 SHEET A-2. THE MAXIMUM DESIGN PRESSURE ON THE PRODUCT
 APPROVAL IS +45 / -45 PSF. FBC R301.2.1 ALSO THE
 INSTALLATION INSTRUCTIONS ARE INCOMPLETE. WHEN
 DOWNLOADING THEY HAVE TO BE SHRUNK TO FIT ON 8.5 X 11
 PAPER.
  
 11) SHOW COMPLIANCE WITH FBCR 301.2.1.2 FOR IMPACT
 PROTECTION OF GLAZED OPENINGS. SUBMIT (2) TWO COPIES OF
 A PRODUCT APPROVAL FOR STORM PANELS, A KEY PLAN AND AN
 INSTALLATION SCHEDULE.
  