2012-02-08 13:19:182007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE FIRST FLOOR BATHROOM IS NOT VENTED PROPERLY. A
 SOIL STACK CAN NOT BE USED AS A STACK VENT. A DRY VENT
 CONNECTION TO THE HORIZONTAL WET VENT IS REQUIRED. SEE
 FBCR P3108.1
  
 2) ONLY THE FIXTURES WITHIN TWO BATHROOM GROUPS ON THE
 SAME FLOOR ARE PERMITTED TO BE VENTED BY A HORIZONTAL
 WET VENT PER FBCR P3108.1. THE PLANS SHOW THE WASHING
 MACHINE DRY VENT BEING USED AS A HORIZONTAL WET VENT
 FOR BATHROOM FIXTURES.
  