| 2012-02-08 13:19:18 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY PLUMBING | | | | | | 1) THE FIRST FLOOR BATHROOM IS NOT VENTED PROPERLY. A | | | SOIL STACK CAN NOT BE USED AS A STACK VENT. A DRY VENT | | | CONNECTION TO THE HORIZONTAL WET VENT IS REQUIRED. SEE | | | FBCR P3108.1 | | | | | | 2) ONLY THE FIXTURES WITHIN TWO BATHROOM GROUPS ON THE | | | SAME FLOOR ARE PERMITTED TO BE VENTED BY A HORIZONTAL | | | WET VENT PER FBCR P3108.1. THE PLANS SHOW THE WASHING | | | MACHINE DRY VENT BEING USED AS A HORIZONTAL WET VENT | | | FOR BATHROOM FIXTURES. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|