Plan Review Notes
Plan Review Notes For Permit 12010282
Permit Number 12010282
Review Stop M
Sequence Number 1
Notes
Date Text
2012-02-09 07:14:262007 FBC W/2009 REVISIONS
  
 DENIED BY MECHANICAL
  
 1) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORM.
  
 2) FBCR M1602.4 REQUIRES THROUGH THE WALL TRANSFER
 GRILLES TO USE 50 SQUARE INCHES OF GRILL AREA TO 100
 CFMS FOR SIZING WITH AN UNRESTRICTED 1 INCH
 UNDERCUTTING OF DOORS TO ACHIEVE PROPER RETURN AIR
 BALANCE. THE FIRST FLOOR OFFICE HAS 292 CFMS AND ONLY
 100 SQUARE INCHES OF GRILL AREA. PLEASE CORRECT.
  