| Plan Review Notes For Permit 12010282 |
| Permit Number |
12010282 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-02-09 07:14:26 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY | | | CALCULATION FORM. | | | | | | 2) FBCR M1602.4 REQUIRES THROUGH THE WALL TRANSFER | | | GRILLES TO USE 50 SQUARE INCHES OF GRILL AREA TO 100 | | | CFMS FOR SIZING WITH AN UNRESTRICTED 1 INCH | | | UNDERCUTTING OF DOORS TO ACHIEVE PROPER RETURN AIR | | | BALANCE. THE FIRST FLOOR OFFICE HAS 292 CFMS AND ONLY | | | 100 SQUARE INCHES OF GRILL AREA. PLEASE CORRECT. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|