| Plan Review Notes For Permit 12010282 |
| Permit Number |
12010282 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-30 15:00:34 | 12010182 | | | 1805 FLORIDA AVE | | | INTERIOR RENOVATION | | | | | | INDICATE LOCATION OF THE ELECTRICAL SERVICE. NEC 215.5 | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | | ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE | | | HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE | | | A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET | | | OF EACH ROOM USED FOR SLEEPING. FBC R313 | | | INDICATE THAT ALL NEW RECEPTACLES WILL BE TAMPER | | | RESISTANT. NEC 406.11 | | | ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE | | | PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC | | | 210.12 | | | BATHROOMS EACH REQUIRE A DEDICATED 20 AMP BRANCH | | | CIRCUIT. NEC 210.11 (C) (3) | | | AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN | | | SERVICE GROUND NEC 250.94 | | | KITCHEN GFCI RECEPTACLE REQUIRED AT ISLAND COUNTER TOP. | | | NEC 210.52 | | | ADDITIONAL RECEPTACLES REQUIRED FOR ANY WALL SPACE MORE | | | THAN 2 FEET IN WIDTH I.E. KITCHEN AND LIVING ROOM. NEC | | | 210.52 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|