Review Stop E
Sequence Number 1
Notes
Date Text
2012-01-30 15:00:3412010182
 1805 FLORIDA AVE
 INTERIOR RENOVATION
  
 INDICATE LOCATION OF THE ELECTRICAL SERVICE. NEC 215.5
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. FBC R313
 INDICATE THAT ALL NEW RECEPTACLES WILL BE TAMPER
 RESISTANT. NEC 406.11
 ALL NEW GENERAL PURPOSE BRANCH CIRCUITS MUST BE
 PROTECTED WITH ARC FAULT CIRCUIT INTERRUPTERS. NEC
 210.12
 BATHROOMS EACH REQUIRE A DEDICATED 20 AMP BRANCH
 CIRCUIT. NEC 210.11 (C) (3)
 AN INTERSYSTEM BONDING STRIP IS REQUIRED AT THE MAIN
 SERVICE GROUND NEC 250.94
 KITCHEN GFCI RECEPTACLE REQUIRED AT ISLAND COUNTER TOP.
 NEC 210.52
 ADDITIONAL RECEPTACLES REQUIRED FOR ANY WALL SPACE MORE
 THAN 2 FEET IN WIDTH I.E. KITCHEN AND LIVING ROOM. NEC
 210.52
  