2012-02-10 10:07:212007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE ENERGY CALCULATION FORM DOES NOT CORRESPOND WITH
 THE PLANS. THE ENERGY CALC. FORM LISTS R-20 CEILING
 INSULATION, R-13 WALL INSULATION, R-0 SLAB FLOOR
 INSULATION AND R-13 RAISED FLOOR INSULATION. THE TWO
 STORY WALL SECTION ON PLAN SHEET A-5 HAS R-30 CEILING
 INSULATION, R-11 WALL INSULATION AND NO INSULATION IN
 THE RAISED FLOOR. PLEASE CORRECT.
  
 2) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORM.
  
 3) THE NEW FOOTINGS ARE REQUIRED TO BE TREATED FOR
 TERMITES. SHOW COMPLIANCE WITH FBC R320.
  
 4) ON THE FOUNDATION PLAN ON SHEET A-5, THE F1 FOOTER
 FOR THE NEW BEARING WALL IS INCORRECTLY SPECIFIED AS
 36" X 36" X 12" W/#5 @ 8" OC. IT SHOULD BE 24" X 12"
 CONC. FOOTER W/3 #5 BARS. PLEASE CORRECT.
  
 5) ON SHEET A-6 THE ROOF NOTES LOADING FOR THE NEW
 STRUCTURAL MEMBERS IS ILLEGIBLE. PLEASE CORRECT. CITY
 AMENDMENTS 106.1
  
 6) ON SHEET A-6 THE ADDED STRAP DETAIL IS FOR ATTACHING
 THE TRUSS TO A CONCRETE BEAM, HOWEVER, THIS STRUCTURE
 IS WOOD FRAME. PLEASE CORRECT. CITY AMENDMENTS 106.1
  
 7) PROVIDE COMPLETE DETAILS FOR THE NEW FIRE PLACE AND
 CHIMNEY SHOWN ON THE PLANS, INCLUDING STRUCTURAL
 DRAWINGS. CITY AMENDMENTS 106.1 & FBCR M1805
  
 8) SHOW COMPLIANCE WITH FBC R313.2.1 AND R313.4 FOR
 SMOKE ALARMS AND CARBON MONOXIDE PROTECTION.
  
 9) SUBMIT TWO COMPLETE SETS OF PRODUCT APPROVALS FOR
 THE EXTERIOR FRENCH DOORS AS REQUIRED BY DCA RULE 9N-3.
  
 10) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE
 SINGLE HUNG WINDOWS DO NOT MEET THE NEGATIVE COMPONENT
 AND CLADDING PRESSURE OF - 47.2 PSF SPECIFIED ON PLAN
 SHEET A-2. THE MAXIMUM DESIGN PRESSURE ON THE PRODUCT
 APPROVAL IS +45 / -45 PSF. FBC R301.2.1 ALSO THE
 INSTALLATION INSTRUCTIONS ARE INCOMPLETE. WHEN
 DOWNLOADING THEY HAVE TO BE SHRUNK TO FIT ON 8.5 X 11
 PAPER.
  
 11) SHOW COMPLIANCE WITH FBCR 301.2.1.2 FOR IMPACT
 PROTECTION OF GLAZED OPENINGS. SUBMIT (2) TWO COPIES OF
 A PRODUCT APPROVAL FOR STORM PANELS, A KEY PLAN AND AN
 INSTALLATION SCHEDULE.
  
 12) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW
 EACH OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  