| Plan Review Notes For Permit 12010249 |
| Permit Number |
12010249 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-12 13:30:52 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS. | | | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. | | | | | | 1- PLEASE PROVIDE SIGNED AND SEALED RAS 117 | | | CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER | | | AREAS AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE | | | OF NOA 10-1230.02 SUBMITTED. NEED THE NAIL ENHANCING | | | CALCULATIONS TO MEET THE DESIGN PRESSURES AS REQUIRED | | | BY SEC. R301.2.1.4.3. | | | | | | ***NOTE: DESGIN PROFESSIONAL DOING THE RAS 117 | | | CALCULATIONS TO TAKE INTO CONSIDERATION THAT THIS | | | BUILDINGIS LOCATED ON EXPOSURE "C". | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|