Plan Review Notes
Plan Review Notes For Permit 12010247
Permit Number 12010247
Review Stop B
Sequence Number 1
Notes
Date Text
2012-01-12 14:36:58RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- EXISTING HOUSE HAS SHINGLES. PROPOSED ROOF IS
 CONCRETE TILE. PROVIDE ENGINEERING SHOWING THAT
 EXISTING HOUSE WILL SAFELY SUPPORT THE ADDITIONAL
 LOADING OF THE CONCRETE TILES. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC.
 PROVIDE 2 SIGNED AND SEALED COPIES. SEC. 417 FLORIDA
 STATUTE.
  
 2- PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL FOR THE
 CONCRETE TILE TO BE INSTALLED. ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE WAS SUBMITTED. DCA RULE 9N-3.
 PROVIDE 2 COPIES.
  
 3- PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL FOR THE
 POLYFOAM TO BE USED. ONLY THE FLORIDA PRODUCT APPROVAL
 COVER PAGE WAS SUBMITTED. DCA RULE 9N-3. PROVDE 2
 COPIES.
  
 4- FLAT ROOF:
 A) PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL FOR THE
 GAF SYSTEM TO BE INSTALLED. ONLY THE FLORIDA PRODUCT
 APPROVAL COVER PAGE WAS SUBMITTED. AND, CLEARLY
 IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO BE
 INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN
 PRESSURES OF SEC. R301.2.1.4.3. DCA RULE 9N-3.
  
 B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY NOTE #8 OF FLORIDA PRODUCT APPROVAL
 SUBMITTED. NEED TO MEET THE DESIGN PRESSURES REQUIRED
 BY SEC. R301.2.1.4.3.
 ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117
 CALCULATIONS TO TAKE INTO CONSIDERATION THAT THIS
 BUILDING IS LOCATED ON EXPOSURE "C".
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712