| 2012-01-12 14:36:58 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW COMMENTS. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- EXISTING HOUSE HAS SHINGLES. PROPOSED ROOF IS |
| | CONCRETE TILE. PROVIDE ENGINEERING SHOWING THAT |
| | EXISTING HOUSE WILL SAFELY SUPPORT THE ADDITIONAL |
| | LOADING OF THE CONCRETE TILES. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC. |
| | PROVIDE 2 SIGNED AND SEALED COPIES. SEC. 417 FLORIDA |
| | STATUTE. |
| | |
| | 2- PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL FOR THE |
| | CONCRETE TILE TO BE INSTALLED. ONLY THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE WAS SUBMITTED. DCA RULE 9N-3. |
| | PROVIDE 2 COPIES. |
| | |
| | 3- PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL FOR THE |
| | POLYFOAM TO BE USED. ONLY THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE WAS SUBMITTED. DCA RULE 9N-3. PROVDE 2 |
| | COPIES. |
| | |
| | 4- FLAT ROOF: |
| | A) PROVIDE COMPLETE FLORIDA PRODUCT APPROVAL FOR THE |
| | GAF SYSTEM TO BE INSTALLED. ONLY THE FLORIDA PRODUCT |
| | APPROVAL COVER PAGE WAS SUBMITTED. AND, CLEARLY |
| | IDENTIFY WHICH APPROVED ASSEMBLY IS GOING TO BE |
| | INSTALLED TO VERIFY COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301.2.1.4.3. DCA RULE 9N-3. |
| | |
| | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR |
| | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS |
| | REQUIRED BY NOTE #8 OF FLORIDA PRODUCT APPROVAL |
| | SUBMITTED. NEED TO MEET THE DESIGN PRESSURES REQUIRED |
| | BY SEC. R301.2.1.4.3. |
| | ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117 |
| | CALCULATIONS TO TAKE INTO CONSIDERATION THAT THIS |
| | BUILDING IS LOCATED ON EXPOSURE "C". |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |