| 2012-01-24 14:00:59 | PLANS DENIED | | | 1) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS PER | | | TABLE 403.3 FBC (M) 2007 | | | 2) REFER TO SECTION 13-409.AB.3.3 SHUT OFF DAMPER | | | CONTROLS. 2007 ENERGY CODE. | | | 3) PROVIDE A DETAIL ON THE MINI SPLIT CONDENSER TIE | | | DOWN PER SECTION 301.12 WIND RESISTANCE | | | 2007 FBC (M) . | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|