Plan Review Notes
Plan Review Notes For Permit 12010238
Permit Number 12010238
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-01-23 11:57:49225 CLEMATIS STREET - SUITE #202
 PERMIT #12010238
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET FP-1 NOT SUBMITTED.
  
 PROVIDE ADDITIONAL PORTABLE FIRE EXTINGUISHERS.
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC
 AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER
 COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT
 EXCEED 75 FEET.
  
 SHEET A1.0: UPDATE THE CODE LIST TO REFERENCE THE 2010
 EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH
 CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101
 WITH FLORIDA AMENDMENTS.
  
 SHEET FA1.01: UPDATE THE STANDARDS LIST TO REFERENCE
 THE 2007 EDITION OF NFPA 72.
  
 SHEET FA1.01: ONLY TWO HORN-TYPE NOTIFICATION
 APPLIANCES LOCATED IN TENANT SPACE; RECOMMEND CHANGING
 THE STROBE-ONLY DEVICE TO HORN-STROBE DEVICE IN BREAK
 ROOM TO HELP MEET THE MINIMUM AUDIBILITY REQUIREMENTS
 OF NFPA 72.
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  