| Plan Review Notes For Permit 12010238 |
| Permit Number |
12010238 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-23 11:57:49 | 225 CLEMATIS STREET - SUITE #202 | | | PERMIT #12010238 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SHEET FP-1 NOT SUBMITTED. | | | | | | PROVIDE ADDITIONAL PORTABLE FIRE EXTINGUISHERS. | | | EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC | | | AND SHALL BE TAGGED BY A LICENSED FIRE EXTINGUISHER | | | COMPANY. TRAVEL DISTANCE TO EXTINGUISHERS SHALL NOT | | | EXCEED 75 FEET. | | | | | | SHEET A1.0: UPDATE THE CODE LIST TO REFERENCE THE 2010 | | | EDITION OF THE FLORIDA FIRE PREVENTION CODE WHICH | | | CONTAINS THE 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 | | | WITH FLORIDA AMENDMENTS. | | | | | | SHEET FA1.01: UPDATE THE STANDARDS LIST TO REFERENCE | | | THE 2007 EDITION OF NFPA 72. | | | | | | SHEET FA1.01: ONLY TWO HORN-TYPE NOTIFICATION | | | APPLIANCES LOCATED IN TENANT SPACE; RECOMMEND CHANGING | | | THE STROBE-ONLY DEVICE TO HORN-STROBE DEVICE IN BREAK | | | ROOM TO HELP MEET THE MINIMUM AUDIBILITY REQUIREMENTS | | | OF NFPA 72. | | | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER | | | SYSTEM AND/OR FIRE ALARM SYSTEM. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|