| Plan Review Notes For Permit 12010238 |
| Permit Number |
12010238 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-19 14:16:27 | BUILDING PROVISO: | | | | | | 1) SHEET A1.0 FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, | | | FIRE PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR | | | ANY OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS | | | SHALL BE EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH | | | SIGNS OR STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDENTIFICATION | | | SHALL BE ABOVE ANY DECORATIVE CEILING AND IN CONCEALED | | | SPACES. SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: | | | "FIRE AND SMOKE BARRIER - PROTECT ALL OPENINGS." | | | | | | 2) SHEET A3.0 BREAKROOM ELEVATION C MICROWAVE/ 11-4.27 | | | CONTROLS AND OPERATING MECHANISMS. | | | 11-4.27.2 CLEAR FLOOR SPACE. CLEAR FLOOR SPACE | | | COMPLYING WITH SECTION 11-4.2.4 THAT ALLOWS A FORWARD | | | OR A PARALLEL APPROACH BY A PERSON USING A WHEELCHAIR | | | SHALL BE PROVIDED AT CONTROLS, DISPENSERS, RECEPTACLES | | | AND OTHER OPERABLE EQUIPMENT. | | | | | | 11-4.27.3 HEIGHT. THE HIGHEST OPERABLE PART OF | | | CONTROLS, DISPENSERS, RECEPTACLES, AND OTHER OPERABLE | | | EQUIPMENT SHALL BE PLACED WITHIN AT LEAST ONE OF THE | | | REACH RANGES SPECIFIED IN SECTIONS 11-4.2.5 AND | | | 11-4.2.6. ELECTRICAL AND COMMUNICATIONS SYSTEM | | | RECEPTACLES ON WALLS SHALL BE MOUNTED NO LESS THAN 15 | | | INCHES (380 MM) ABOVE THE FLOOR. |
|