2012-01-31 16:00:18RESIDENTIAL ADDITON BUILDING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- .PLEASE PROVIDE CURRENT 2008 REVISED ENERGY
 CALCUALTIONS FORM. FORM 600C-01 IS NO LONGER USED.
  
 2- PLEASE BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG
 RD.) TO VERIFY IF IMPACT FEES ARE DUE. THEN, BRING BACK
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
  
 3- ENGINEER TO UPDATE THE CERTIFICATE OF AUTHORIZATION
 FOR THE S.W. ENGINEERING INC. FIRM. ENGINEER TO CONTACT
 THE DEPARTMENT OF BUSINESS & PROFESSIONAL REGULATION
 (DBPR) AND UPDATE AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTE AND SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE
 CODE FOR ENGINEERS.
  
 4- SHEET 3.0: WALL LEGEND FOR WALL #2 CALLS FOR 2X4
 STUDS AND R-19 MIN. INSULATION. R-19 INSULATION DOESN'T
 FIT ON 2X4 WALL. REVISE AS REQUIRED AND COORDINATE WITH
 THE REVISED ENERGY CALCULATIONS. SEC. 106.1.1 CITY
 AMENDMENTS TO FBC.
  
 5- SHEET 3.1: REVISE DETAIL LEGEND #5. NEED TO PROVIDE
 7/8" STUCCO THICKNESS, NOT 3/4". TABLE R702.1(1).
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR ALL THE SIMPSON STRUCTURAL CONNECTORS
 SPECIFIED BY THE ENGINEER ON PLANS AND DETAILS. PLEASE
 PROVIDE ONLY THE 2007 CODE VERSION PRODUCT APPROVAL
 COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR.
  