| 2012-01-31 16:00:18 | RESIDENTIAL ADDITON BUILDING REVIEW COMMENTS. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- .PLEASE PROVIDE CURRENT 2008 REVISED ENERGY |
| | CALCUALTIONS FORM. FORM 600C-01 IS NO LONGER USED. |
| | |
| | 2- PLEASE BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG |
| | RD.) TO VERIFY IF IMPACT FEES ARE DUE. THEN, BRING BACK |
| | STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 3- ENGINEER TO UPDATE THE CERTIFICATE OF AUTHORIZATION |
| | FOR THE S.W. ENGINEERING INC. FIRM. ENGINEER TO CONTACT |
| | THE DEPARTMENT OF BUSINESS & PROFESSIONAL REGULATION |
| | (DBPR) AND UPDATE AS REQUIRED BY CHAPTER 471 FLORIDA |
| | STATUTE AND SEC. 61G15-23.002 FLORIDA ADMINISTRATIVE |
| | CODE FOR ENGINEERS. |
| | |
| | 4- SHEET 3.0: WALL LEGEND FOR WALL #2 CALLS FOR 2X4 |
| | STUDS AND R-19 MIN. INSULATION. R-19 INSULATION DOESN'T |
| | FIT ON 2X4 WALL. REVISE AS REQUIRED AND COORDINATE WITH |
| | THE REVISED ENERGY CALCULATIONS. SEC. 106.1.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 5- SHEET 3.1: REVISE DETAIL LEGEND #5. NEED TO PROVIDE |
| | 7/8" STUCCO THICKNESS, NOT 3/4". TABLE R702.1(1). |
| | |
| | 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR ALL THE SIMPSON STRUCTURAL CONNECTORS |
| | SPECIFIED BY THE ENGINEER ON PLANS AND DETAILS. PLEASE |
| | PROVIDE ONLY THE 2007 CODE VERSION PRODUCT APPROVAL |
| | COVER PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |