| Plan Review Notes For Permit 12010224 |
| Permit Number |
12010224 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-18 11:19:00 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE ORIGINAL MECHANICAL PLANS ARE SIGNED AND SEALED | | | BY THE ARCHITECT, FERNANDO PRIETO. ANY REVISIONS TO THE | | | PLANS ARE REQUIRED TO BE SIGNED AND SEALED BY HIM PER | | | FS 481. | | | | | | 2) THE REVISED PLANS HAVE CONFLICTING EQUIPMENT | | | SCHEDULES. ONE IS FOR GOODMAN UNITS AS SPECIFIED ON THE | | | ORIGINAL PLANS AND THE OTHER IS FOR CARRIER UNITS. | | | PLEASE REMOVE THE ONE THAT IS NOT BEING INSTALLED FROM | | | THE PLANS. CITY AMENDMENTS 106.1.1 | | | | | | 3) THE PROJECT SUMMARY AND LOAD CALCULATIONS FROM | | | CONNIE'S E-CALCS SPECIFY GOODMAN EQUIPMENT. IF CARRIER | | | EQUIPMENT IS USED, REVISED CALCULATIONS ARE REQUIRED. | | | 2007 ENERGY GLITCH AMENDMENTS SECTION N1107.AB. | | | | | | 4) THE CONTRACTOR/COMPANY SPECIFIED ON THE PLANS, | | | TROPICAL A/C & HTG. IS NOT THE CONTRACTOR/COMPANY THAT | | | IS LISTED ON THE PERMIT APPLICATION. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|