| 2012-01-12 11:44:52 | 505 CLEMATIS STREET | | | PERMIT #12010219 | | | MASTER #11090836 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE SPRINKLER COVERAGE (X2) IN THE EXISTING CEILING | | | OF THE ENTRY DOOR AS THE EXISTING UPRIGHT SPRINKLERS DO | | | NOT APPEAR TO PROTECT THIS AREA DUE TO THE POSSIBLE | | | SPRAY OBSTRUCTION CREATED BY THE EXISTING BEAM. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|