2012-04-05 15:25:15BUILDING REVIEW APPROVED WITH PROVISO:
  
 1- THIS PROPERTY IS LOCATED ON FLOOD ZONE A5 WITH A
 BASE FLOOD ELEVATION OF 7'-0". SURVEY STATES HOUSE
 FINISH FLOOR 7.5' AND GARAGE 6.6'. SINCE GARAGE FLOOR
 IS BELOW 7.5', THEN FLOOD DAMAGE -RESISTANT MATERIALS
 NEED TO BE USED IN GARAGE WALLS. FLOOD VENTS WILL BE
 REQUIRED. SEE FEMA FLOOD DAMAGE-RESISTANT MATERIALS
 REQUIREMENTS AND PROVIDE INFORMATION SHOWING COMPLIANCE
 WITH THIS REQUIREMENTS. SEC. 94-546 OF CITY FLOOD
 MANAGEMENT POLICY.
  
 2- SURVEY SUBMITTED: A) REVISE FLOOD ZONE SPECIFIED.
 BUILDING IS LOCATED ON FLOOD ZONE "A5" NOT "A6".
 B) PROVIDE SURVEYS WITH ORIGINAL SIGNATURE (NOT COPY)
 AS REQUIRED BY CHAPTER 472 FLORIDA STATUTES.
  
 3- REVISE ENERGY CALCULATIONS: PAGE 2 OF 5 SPECIFIES
 COMPOSITION SHINGLES ON THE ROOF. PLANS SHOW METAL
 ROOFING. REVISE AS REQUIRED AND OWNER/AGENT TO SIGN AND
 DATE BOTTOM OF FORM.
  
 4- FLAT ROOF FLORIDA PRODUCT APPROVAL FL1654-R10
 SUBMITTED: PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS AS REQUIRED BY NOTE #8 ON PAGE 2 OF 30 OF FLORIDA
 PRODUCT APPROVAL SUBMITTED.
  