2012-02-06 14:19:03RESIDENTIAL (R3) ADDITION/RENOVATION MECHANICAL REVIEW
 COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- MECHANICAL CONTRACTOR SIGNED THE PERMIT APPLICATION,
 BUT THERE ARE NOT DRAWINGS SHOWING A/C WORK. PLEASE
 PROVIDE A/C DRAWING AND A/C EQUIPMENT SIZING
 CALCULATIONS AS REQUIRED BY SEC. N1107.AB.1.
 ***NOTE: A/C CONTRACTOR MAY DRAW PLANS. PLEASE PROVIDE
 CONTRACTOR'S NAME, LICENSE NUMBER AND SIGN THE
 DRAWINGS.
  