2012-02-01 14:25:58RESIDENTIAL (R3) RENOVATION/ALTERATION BUILDING REVIEW
 COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- PROVIDE COMPLETE SET OF PLANS AND SPECIFICATIONS TO
 SHOW ALL WORK TO BE PERFORMED AS SPECIFIED ON THE
 DESCRIPTION OF PROJECT SHOWN ON THE CONSTRUCTION
 AGREEMENT SUBMITTED. SEC. 106.1.1 CITY AMENDMENTS TO
 FBC.
  
 A) SHOW DEMOLITION AND REBUILDING OF WALLS.
 B) SHOW HALF CONCRETE WALL AND FRAME OUT FOR OFFICE
 AREA.
 C) SHOW ATTIC PULL DOWN STAIRS LOCATION, FRAMING
 DETAILS, ETC. AND, PROVIDE ENGINEERING SHOWING THAT
 EXISTING ROOF SYSTEM IS CAPABLE OF SUPPORTING
 ADDITIONAL LOAD (STORAGE). SHOW COMPLIANCE WITH TABLE
 R301.5 FOR ATTIC WITH STORAGE LIVE LOAD. SEE FOOTNOTES
 ALSO.
 D) SHOW DEMOLITION AND REBUILDING OF MASTER BATH.
 E0 SHOW WINDOW REPAIRS/SPECIFICATIONS.
 F) SHOW ROOF REPAIRS/SPECIFICATIONS.
  
 2- THIS PROPERTY IS LOCATED ON FLOOD ZONE A5. IF THE
 WORK EXCEEDS 50% OF THE VALUE OF THE STRUCTURE, THIS
 VALUE IS CUMULATIVE ON THE LIFE OF THE STRUCTURE. THEN,
 THE ALL HOUSE NEEDS TO COMPLY WITH THE CITY FLOOD
 MANAGEMENT POLICY. THIS IS ANOTHER REASON WHY THE PLANS
 SHOWING THE SPECIFIC WORK TO BE PERFORMED IS REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  