| Plan Review Notes For Permit 12010196 |
| Permit Number |
12010196 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-11-05 12:07:38 | 12010196 | | | 1860 N. TAMARIND AVE. | | | MULTIFAMILY DWELLING | | | | | | PLEASE PROVIDE A RESPONSE TO THE FOLLOWING ELECTRICAL | | | REVIEW COMMENTS. | | | | | | ADD A SMALL APPLIANCE CIRCUIT TO THE PANEL SCHEDULE FOR | | | UNITS ?A? AND ?D?. NEC 210.52 (C). (THIS WAS PREVIOUSLY | | | NOTED DURING THE LAST REVIEW WITH A WRITTEN RESPONSE. | | | AN REVISION TO SHEET E# WAS NOT PROVIDED) | | | | | | THE CHANGES TO THE ELECTRICAL DESIGN FOR THE APARTMENT | | | ELECTRICAL SERVICE HAS PROMPTED SOME ADDITIONAL REVIEW | | | COMMENTS LISTED BELOW. | | | | | | A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED | | | BY ONLY ONE SERVICE. NEC 230.2 | | | MEANS SHALL BE PROVIDED TO DISCONNECT ALL CONDUCTORS IN | | | A BUILDING. NEC 230.70 | | | THE SERVICE DISCONNECTING MEANS SHALL CONSIST OF NOT | | | MORE THAT SIX SWITCHES. NEC 230.71 | | | THE TWO TO SIX DISCONNECTS AS PERMITTED SHALL BE | | | GROUPED IN ONE LOCATION. NEC 230.72 | | | | | | ROBERT LECKY | | | ELECTRIC PLAN REVIEWER | | | [email protected] | | | 561-805-6718 | | | | | | |
|