| 2012-10-31 10:54:21 | BUILDING PLAN REVIEW |
| | PERMIT: 12010196 |
| | ADD: 1860 N TAMARIND AVE. |
| | CONT: HARTNETT BUILDING GROUP |
| | TEL: (561)523-5902 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2ND REVIEW |
| | OCT. 31/ 2012 |
| | ACTION: DENIED |
| | |
| | 1) 11/09/2012 COMPLIED, AARCHITECT RED LINED PLANS. |
| | SHEET A1.1 SEMI- COMPLIED. THE PLANS ARE MISSING THE |
| | ACCESS AISLE AS REQUIRED BY ANSI 4.6. SITE PLAN DOES |
| | NOT COMPLIANCE WITH THE FAIR HOUSING ACT, AND ANSI |
| | A117.1 4.3 ACCESSIBLE ROUTE, AN ACCESSIBLE ROUTE TO ALL |
| | SITE AMENITIES (DUMPSTER), PARKING SPACES, ACCESS |
| | AISLES, CURB RAMPS, RAMPS SLOPES, CROSS SLOPES & |
| | ACCESIBILTY TO PUBLIC TRANS PORTATION. |
| | \ |
| | |
| | 12) COMPLIED. 11/14/2012 CLARIFICATION LETTER FROM |
| | ONMJ. |
| | 2ND REQUEST. SHEET S1 VERSES SHEET A2.1 DOOR # 2 IS |
| | INDICATED AS A 6'-0" WIDE DOOR OPENING, WHERE AS S1 |
| | INDICATES TTHE BLOCK OPENING TO BE NARROWER. PLEASE |
| | ALSO REVIEW THE BEAM SCHEDULE ON S3, VERSES S1 AND S2 |
| | ALL BEAMS ARE LABELED BB-1 WITH NO STIRRUPS OR HOOPS |
| | (HAIRPINS DETAIL 4 / SHEET S4) ) OVER THE WINDOWS AND |
| | DOORS. ACI 530 # 7.5.3.1 SHEAR REINFORCEMENT SHALL BE |
| | PROVIDED PARALLEL TO THE DIRECTION OF APPLIED FORCE. |
| | SPACING OF SHEAR REINFORCEMENT SHALL NOT EXCEED THE |
| | LESSEER OF D/2 OR 48 INCHES. |
| | |
| | 13-15) COMPLIED. |
| | |
| | 16) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | NEW COMMENTS |
| | |
| | 17) 11/09/2012 COMPLIED, AARCHITECT RED LINED PLANS. |
| | SHEET A2.1 PLEASE REVIEW EGRESS WINDOW NOTE IN REGARDS |
| | TO TOTAL GLAZED AREA VERSES THE REQUIRED CLEAR OPENING |
| | REQUIREMENTS FOR FIRST FLOOR VERSES SECOND FLOOR. 2007 |
| | FBC-B SECTION 1026.2. |
| | |
| | 18) PROVISO: 11/09/2012 ARCHITECT IS LOOK AT OPTIONS |
| | FOR SAFETY GLAZING. |
| | SHEET A2.1 WINDOW SCHEDULE NOTE # 3 INDICATES ALL |
| | SAFETY GLAZING IN HAZARDOUS AREAS SHALL BE TEMPERED. |
| | THE WINDOW SCHEDULE DOES INDICATE |
| | WINDOW TYPE E BUT NOT TYPE A WHERE THE WINDOW WILL BE |
| | NEXT TO THE STAIR IS THE DESIGNER USING THE LARGE |
| | MISSILE TESTED LAMINATED GLAZING AS MEETING THE SAFETY |
| | GLAZING REQUIREMENTS UNDER 2406.4. |
| | |
| | 19) 11/14/2012 LETTER FROM ARCHITECT DAVID LAWRENCE TO |
| | DOUG WISE B.O. ASKING FOR REVIEW OF ALTERNATE MATERIALS |
| | & METHODS, SUBMITTED TO ROBERT BROWNS OFFICE. JW. |
| | |
| | 11/09/2012 ARCHITECT IS TO WRITE LETTER FOR ALTERNATE |
| | MATERIALS AND METHODS 2010 FBC ADMINISTRATIVE CODE |
| | 104.11.THE COVERSHEET A1.0 UNDER THE BUILDING DESIGN |
| | LIST THIS BUILDING AS A TYPE V-B UNSPRINKLERED. BOTH |
| | THE BUILDING AND FIRE CODES REQUIRE ALL R TYPE |
| | OCCUPANCIES TO BE FIRE SPRINKLERED WIT THE EXCEPTION OF |
| | ONE AND TWO FAMILY DWELLINGS THAT ARE REVIEWED UNDER |
| | THE 2007 FBC-R RESIDENTIAL CODE. |
| | 2007-09 FBC-B 903.2.7 REQUIRES FIRE SPRINKLERS. WE DO |
| | UNDERSTAND THERE WAS TALK WITH THE FIRE DEPARTMENT |
| | ABOUT FIRE SPRINKLER REQUIREMENTS BUT NO OTHER |
| | INFORMATION HAS BEEN PROVIDED BY THE FIRE DEPARTMENT AS |
| | TO THE RESULTS OF SUCH MEETING. CHIEF DANIELS HAS |
| | ENTERED IN THE PLAN REVIEW FIELD RESULTS THAT A MEETING |
| | WITH THE DESIGNER HAD OCCURED WHICH HAS KEPT THE PERMIT |
| | ALIVE SINCE THE LAST LISTED ACTIVITY. THE DESIGNER OF |
| | RECORD ON THE COMMENT RESPONCE SHEET INDICATES THEY ARE |
| | GOING WITH A PERFORMANCE BASED METHOD IN LEIU OF FIRE |
| | SPRINKLERS. THE COVER SHEET DOES NOT INDICATE A |
| | PREFORMANCE BASED METHOD VERSES FIRE SPINKLERS. IF THE |
| | DESIGNER OF RECORD IS PROPOSING TO USE ALTERNATE |
| | MATERIALS, DESIGN AND METHODS OF CONSTRUCTION (104.11 |
| | WEST PALM BEACH ADMINISTRATIVE CODE) A LETTER TO THE |
| | BUILDING OFFICIAL REQUESTING THE USE OF ALTERNANTE |
| | MATERIAL AND METHODS TO BE SUBSTITUTED. WHEN ALTERNANTE |
| | LIFE SAFETY SYSTEMS ARE DESIGNED, THE SFPE ENGINEERING |
| | GUIDE OF PERFORMANCE- BASED FIRE PROTECTION ANALYSIS |
| | AND DESIGN OF BUILDINGS OR OTHER METHODS APPROVED BY |
| | THE BUILDING OFFICIAL MAY BE USED. |
| | |
| | NOTE NO PRODUCT APPROVALS HAVE BEEN SUBMITTED FOR |
| | ROOFING AT THIS TIME, A SEPERATE PERMIT, REVIEW AND |
| | ASSOCIATED FEES SHALL OCCUR. |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |