| 2012-01-18 11:04:50 | PLEASE SUBMIT AN ELECTRICAL DETAIL FOR THE ILLUMINATION | | | OF THE NEW SIGN. EACH SIGN FEEDER CIRCUIT SHALL BE | | | CONTROLLED BY ONE OR MORE SWITCHES THAT ARE WITHIN SITE | | | OF THE CONTROLLER AND ALSO WITH IN SIGHT OF THE SIGN. | | | NEC 600.6 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|