| 2012-01-24 17:37:50 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- MISSING BASIC INFORMATION. ARCHITECT TO SPECIFY ALL |
| | THE DESIGN CRITERIA AND CODE USED FOR THE DESIGN OF THE |
| | ROOF ADDITION. SPECIFY THE BUILDING CODE, WIND SPEED, |
| | BUILDING EXPOSURE, DESIGN PRESSURES AND DEAD AND LIVE |
| | LOADS AS REQUIRED BY SEC. R301 OF 2007 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | ***NOTE: ACCORDING TO SEC. R301.2.1.4.3 THIS BUILDING |
| | IS LOCATED ON EXPOSURE "C". TAKE THIS INTO |
| | CONSIDERATION FOR THE DESIGN OF THE ADDITION. |
| | |
| | |
| | 2- ARCHITECT TO PROVIDE ALL HIS INFORMATION ON THE |
| | TITLE BLOCK AS REQUIRED BY SEC. 61G1-16.004 OF FLORIDA |
| | ADMINISTRATIVE CODE AND CHAPTER 481 OF FLORIDA |
| | STATUTES. INFORMATION WAS NOT PROVIDED ON THE PLANS |
| | SUBMITTED. |
| | |
| | 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) SHINGLES NOA 11-0411.02 SUBMITTED WAS SUPERSEDED BY |
| | MIAMI-DADE. PLEASE VISIT THE MIAMI-DADE WEBSITE AND |
| | DOWNLOAD CURRENT NOA. |
| | |
| | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON THE |
| | PLANS AND DETAILS. PLEASE, PROVIDE ONLY THE FLORIDA |
| | PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING THE |
| | SPECIFIED CONNECTOR. |
| | |
| | 4- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT |
| | SIGNING AND SEALING) ALL PRODUCT APPROVALS PRIOR TO |
| | SUBMITTAL TO THIS OFFICE AS REQUIRED BY SEC. 106.3.3 |
| | CITY AMENDMENTS TO FBC. |
| | |
| | 5- ARCHITECT TO SPECIFY HOW IS THE 4X10 BEAM ATTACHED |
| | TO EXISTING WALL. SEC. R301.2.1.4.3. |
| | |
| | 7- DETAIL B & C: ARCHITECT TO CLARIFY WHY USING 1/4" X |
| | 4" MASONRY ANCHORS INTO EXISTING WOOD STUDS. PROVIDE |
| | COMPLETE ENGINEERING ANALYSIS. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 8- PROVIDE ROOF SHEATHING COMPLETE NAILING |
| | SPECIFICATIONS TO SHOW COMPLIANCE WITH THE DESIGN |
| | PRESSURES OF SEC. R301.2.1.4.3. |
| | |
| | 9- OWNER/BUILDER TO APPLY FOR THE ROOFING PERMIT. OWNER |
| | MAY SIGN THE PERMIT APPLICATION ON THE ROOFING |
| | CONTRACTOR LINE TO GET THE ROOFING PERMIT. |
| | |