| Plan Review Notes For Permit 12010160 |
| Permit Number |
12010160 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-12 14:05:30 | SERVICE IS ON ZERO LOT LINE OF BUILDING. | | | | | | NEED SURVEY AND PERMISSION FROM OWNER OF BUILDING AND | | | OWNER OF PARKING LOT | | | TO HAVE SERVICE ON THAT SIDE OF BUILDING. | | | | | | FAULT CURRENT SUPPLIED STATES 45,159 AMPERES AT FPL | | | NEED 50,000 AIC RATED FUSES/CIRCUIT BREAKER AT MAIN. | | | | | | | | | | | | J. LEAHY 01/12/12 |
|