| 2012-01-26 10:20:49 | PERMIT # 12010158 |
| | ADDRESS: 8020 S DIXIE HWY |
| | CONTRACTOR: CANO INC |
| | TEL: 561-543-1290 |
| | |
| | 2007/09 FBC-BUILDING |
| | 2007/09 EXISTING BUILDING CODE |
| | LEVEL II ALTERATIONS: EXSST BLDG CODE: 701.3 ALL NEW |
| | CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS AND SPACES |
| | SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE- BUILDING. |
| | |
| | 1) SHEET A2.1 THE DETAIL F PARTIAL FOUNDATION PLAN |
| | INDICATES THE USE OF A 8X8 INCH THICKENED EDGE FOR THE |
| | FOUNDATION WHERE AS THIS IS CONSIDERED AN ADDITION WITH |
| | WALL LOADING PLEASE SEE NOTE ON SHEET A3.1 FOUNDATION |
| | NOTE 3, THE FOUNDATION SHALL BE 1?-0? BELOW EXTERIOR |
| | FINISH GRADE, PLEASE ALSO REVIEW FBC-B 1805.2 DEPTH OF |
| | FOUNDATIONS. |
| | |
| | 2) SHEET A2.1 IT APPEARS THERE IS A DISCREPANCY IN THE |
| | PLANS WALL SECTION A SHEET A2.1 INDICATES THE USE OF |
| | 5/8 INCH EXT GRADE PLYWOOD WHERE AS SHEET A3.1 UNDER |
| | THE HEADING OF NOTE 5 PLYWOOD SHEATHING SUB-HEADING A |
| | INDICATES THE USE OF 5/8 INCH EXTERIOR GRADE GYPSUM |
| | SHEATHING. |
| | |
| | 3) PLEASE NOTE IF THE 5/8 INCH EXTERIOR GRADE PLYWOOD |
| | WILL BE INSTALLED COMPLIANCE WITH FBC-B 2304.11.2.6 IF |
| | LESS THAN 6 INCHES BETWEEN THE WALL SHEATHING AND GRADE |
| | SHEATHING, SIDING AND WOOD WALL FRAMING ARE OF |
| | NATURALLY DURABLE WOOD OR PRE-PRESERVATIVE-TREATED |
| | WOOD. |
| | |
| | 4) SHEET A2.1 DETAIL G INDICATES THE USE OF A PRECAST |
| | CONCRETE PAD FOR CONDENSER ON ALUMINUM RACK. PLEASE |
| | PROVIDE PRODUCT APPROVALS FOR THE PRE-CAST CONCRETE PAD |
| | AND FOR THE ALUMINUM RACK, APPROVED FOR USE IN A 140 |
| | MPH WIND ZONE. RULE 9N-03. |
| | |
| | 5) SHEET A2.1 DETAIL B INDICATES THE METAL STUD BEING |
| | ANCHORED INTO A BUILT DOWN HEADER SYSTEM, PLEASE |
| | PROVIDE THE TYPE OF FASTENER TO BE INSTALLED TO ANCHOR |
| | THIS WALL SECTION TO THE EXISTING HEADER. INDICATE TYPE |
| | OF FASTENER, SPACING AND SIZE OF ANCHOR. |
| | |
| | 6A) SHEET A2.1 SECTION G ALSO INDICATES A NEW EXTERIOR |
| | FREEZER DOOR AND THE USE OF STORM SHUTTERS FOR HIGH |
| | WIND EVENTS. |
| | RULE 9N-03 REQUIRES PRODUCT APPROVALS FOR ALL EXTERIOR |
| | DOORS. 9N-03 (31)(A). EVEN THOUGH STORM SHUTTERS ARE TO |
| | BE APPLIED THE STORM SHUTTERS ONLY PROTECT THE FREEZER |
| | DOOR FROM LARGE MISSILE IMPACT NOT FROM POSITIVE & |
| | NEGATIVE PRESSURES. |
| | |
| | 6B) STORM SHUTTERS ALSO REQUIRE PRODUCT APPROVALS RULE |
| | 9N-03(31)(E). |
| | |
| | 7) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9N-03 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |