| Plan Review Notes For Permit 12010122 |
| Permit Number |
12010122 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-03-22 11:48:41 | PLANS DENIED | | | 1) PROVIDE MORE INFORMATION ON THE EQUIPMENT SCHEDULE | | | CONDENSER MODEL NUMBER AND INFORMATION ON THE | | | AIR HANDLER UNIT. SECTION 301.5 FBC (M) 2007 | | | 2) PROVIDE HEAT LOADS AND ENERGY CALCULATIONS FOR THE | | | ADDITION. | | | 3) ON THE DETAIL FOR THE CONDENSER STAND TO ROOF WHAT | | | SIZE BOLTS | | | ARE USED . SECTION 301.12 WIND RESISTANCE.2007 FBC (M) | | | 4) PROVIDE PRODUCT APPROVALS ON THE CONDENSER STAND | | | WITH THE | | | PLANS SECTION 106.3.3 FBC 2007 | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|