| Plan Review Notes For Permit 12010119 |
| Permit Number |
12010119 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-19 09:41:27 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. SPECIFY THE FASTENER SPACING OR FASTENER PATTERN | | | REQUIRED TO RESIST MINIMUM WIND DESIGN CRITERIA | | | FBC1609. NOTE THAT THIS IS A REPEAT COMMENT FOR THIS | | | ENGINEER (JOHN HOLT PE). A SET OF PLANS HAS BEEN | | | RETAINED. | | | | | | 2. PLEASE CLARIFY, 1/4" X 20 STRUD INCLUDED IN THE | | | "SPECIFICATIONS," WHAT IS 20? THE MOUNTING DETAIL SHOWS | | | A MINIMUM 2" EMBEDMENT. IS THIS TO READ 2"? | | | | | | |
|