2012-01-09 16:39:33****CORRECTIONS****
 **REVISED 1/12/12**
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THE ELEVATION WHICH SHOWS LOCATION OF PROPOSED WORK
 DOES NOT INCLUDE THE DOOR. IT APPEARS TO BE
 INCONSISTENT WITH OTHER PERMIT DOCUMENTS.
  
 2. PROVIDE THE OCCUPANCY CLASSIFICATION OF THE SPACE AS
 WELL AS THE OCCUPANT LOAD. THIS CAN BE DETERMINED FOR
 YOU IF A DESCRIPTION OF THE USE OF THE SPACE IS
 PROVIDED WITH A BASIC FLOOR PLAN. THIS MAY BE PROVIDED
 VIA EMAIL. FBC 1008.1.9 AND EXCEPTION. HARDWARE
 REQUIREMENTS CANNOT BE DETERMINED BASED ON INFORMATION
 PROVIDED.
  
 3. PROVIDE BUILDING HEIGHT SO DESIGN PRESSURES CAN BE
 DETERMINED, FBC1609.
  
 4. (NEW COMMENT) SCOPE OF WORK (REMOVAL OF KNEE WALL)
 IS NOT WITHIN THE SCOPE OF A GLASS/GLAZING CONTRACTOR'S
 LICENSE. ADVISED CONTRACTOR VIA EMAIL.
  
  
  
  
  
  
  
  