| Plan Review Notes For Permit 12010023 |
| Permit Number |
12010023 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-24 14:36:24 | 12010023 | | | 734 NEW YORK STREET | | | KITCHEN REMODEL | | | | | | SCOPE OF ELECTRICAL WORK INSUFFICIENTLY DETAILED. | | | PLEASE PROVIDE THE FOLLOWING: | | | | | | INDICATE THE SIZE AND LOCATION OF NEW ELECTRICAL PANEL. | | | PROVIDE A PANEL SCHEDULE AND LOAD CALCULATION. SHOW THE | | | SERVICE LOCATION, FEEDER SIZE AND EXISTING MAIN | | | BREAKER. INCLUDE KITCHEN LAY OUT SHOWING LOCATION OF | | | ALL NEW AND EXISTING RECEPTACLES. IF THIS IS A NEW | | | SERVICE ADDITIONAL INFORMATION MAY BE NEEDED. NEC 215.5 | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | | ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE | | | HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE | | | A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET | | | OF EACH ROOM USED FOR SLEEPING. FBC R313 | | | VERIFY THE KITCHEN COUNTER TOP RECEPTACLES AND BATHROOM | | | RECEPTACLES ARE GFCI PROTECTED. NEC 210.8 | | | INDICATE THAT ALL NEW RECEPTACLES WILL BE TAMPER | | | RESISTANT. NEC 406.11 | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|