2012-01-24 14:36:2412010023
 734 NEW YORK STREET
 KITCHEN REMODEL
  
 SCOPE OF ELECTRICAL WORK INSUFFICIENTLY DETAILED.
 PLEASE PROVIDE THE FOLLOWING:
  
 INDICATE THE SIZE AND LOCATION OF NEW ELECTRICAL PANEL.
 PROVIDE A PANEL SCHEDULE AND LOAD CALCULATION. SHOW THE
 SERVICE LOCATION, FEEDER SIZE AND EXISTING MAIN
 BREAKER. INCLUDE KITCHEN LAY OUT SHOWING LOCATION OF
 ALL NEW AND EXISTING RECEPTACLES. IF THIS IS A NEW
 SERVICE ADDITIONAL INFORMATION MAY BE NEEDED. NEC 215.5
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT
 ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE
 HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE
 A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET
 OF EACH ROOM USED FOR SLEEPING. FBC R313
 VERIFY THE KITCHEN COUNTER TOP RECEPTACLES AND BATHROOM
 RECEPTACLES ARE GFCI PROTECTED. NEC 210.8
 INDICATE THAT ALL NEW RECEPTACLES WILL BE TAMPER
 RESISTANT. NEC 406.11
  