| 2012-01-05 16:24:54 | REROOF AND ROOF COATING BUILDING REVIEW COMMENTS. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | | 11-0126.01 SUBMITTED. SELECTED ASSEMBLY ON PAGES 11 AND | | | 12 OF NOA SUBMITTED IS GOOD FOR -52.5 PSF. NEED TO | | | PROVIDE RAS 117 CALCULATIONS TO MEET THE DESIGN | | | PRESSURES OF SEC. 1609 FBC FOR PERIMETER AND CORNER | | | AREAS. | | | | | | ***NOTE: DESIGN PROFESSIONAL DOING THE CALCULATIONS TO | | | KEEP IN CONSIDERATION THAT ACCORDING TO THE FBC 2009 | | | REVISIONS, THIS BUILDING IS LOCATED ON EXPOSURE "C". | | | | | | 2- ROOF COATING: CLEARLY IDENTIFY WHICH SPECIFIC | | | COATING PRODUCT IS GOING TO BE USED FROM THE NOA | | | 11-0523.02 SUBMITTED TO VERIFY PROPER APPLICATION. SEC. | | | 106.1.1 CITY AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|