2012-02-10 07:58:15BUILDING PLAN REVIEW
 PERMIT:12010011
 ADD: 535 E LAKEWOOD RD
 CONT: NOWAK CONSTRUCTION
 TEL: (561)779-9577
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1) THE CONTRACTOR OF RECORD IF DOING THEIR OWN DESIGN
 (DRAFTING) ARE TO TAKE OWNERSHIP OF THE PLANS PRINT
 THEIR NAME, SIGN THEIR NAME AND PROVIDE THEIR LICENSE
 NUMBER ON THE PLANS BEFORE SUBMITTAL TO THE BUILDING
 DEPARTMENT.
 FBC-B 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
  
 2) 2007/09 FBC-B 106.3.5 MINIMUM PLAN REVIEW CRITERIA
 FOR BUILDINGS. THE EXAMINATION OF THE DOCUMENTS BY THE
 BUILDING OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM
 CRITERIA AND DOCUMENTS:
  
 A) 106.3.5 (3)MINIMUM BUILDING TYPE
  
 B) BUILDING SPRINKLERED OR NON-SPRINKLERED
  
 C) IT APPEARS THERE ARE EITHER SEPERATE TENANTS OR
 OCCUPANCY SEPERATION ISSUES NOT INDICATED ON THE PLANS
 (TABLE 508.3.3)/ 708.1. SEPERATED USE OR NON SEPERATED
 508.3.1.3 OR 508.3.2.
  
 106.3.5(2) OCCUPANCY GROUP ( OCCUPANCY SEPERATION
 ISSUES) AND SPECIAL OCCUPANCY REQUIREMENTS SHALL BE
 DETERMINED. THE PBC PROPERTY APPRAISERS OFFICE
 INDICATES THE FOLLOWING SQ FT AREAS:
 1590 S F OFFICE
 1054 S F GARAGE
 4760 S F WAREHOUSE
  
 D) 106.3.5 (6) LIFE SAFETY OCCUPANT LOADS/ EGRESS
 CAPACITY
  
 E) CHANGE IN CEILING/ ROOF ASSEMBLIES? SHOW OCCUPANCY
 SEPERATION WALL DETAIL AND HOUR RATING!!!!!
  
 F) COMPLIED.
  
 G) PLANS FAIL TO PROVIDE DETAILS FOR ACCESSIBILITY TO
 RESTROOMS AND BREAK ROOM AREAS?PLEASE REVIEW 2007/09
 FBC-B CHAPTER 11-4.1.6(2)(A) 20 % DISPROPORTIONATE
 COST. PLEASE SHOW THE LAYOUT OF THE RESTROOMS SINCE THE
 WALL FINISHES WERE REMOVED!!!!!!!!! DEMO PERMIT
 11120176.
  
 3) PLEASE REVIEW 2007/09 EXISTING BUILDING CODE CHAPTER
 7 FOR LEVEL 2 ALTERATIONS OR IS THIS A LEVEL I
 ALTERATION:
  
 3A) 704.5 EGRESS DOORS.
  
 3B) 706.1. ACCESSIBILITY CHAPTER 11 OF THE FBC-B.
  
 3C) POSSIBLY: 711.1 MINIMUM REQUIREMENTS ENERGY CODE.
  
 4) SUBMITTED DOOR SPEC MASONITE DOOR, PLANS DO NOT
 INDICATE WHERE THIS DOOR IS LOCATED, INTERIOR .
 EXTERIOR , FIRE RATED DOOR THESE ARE ALL UNKNOWNS?
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER