2012-01-09 12:09:151201 ALLENDALE ROAD
 PERMIT #11120766
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION REFERENCES THIS SPACE AS A
 MERCANTILE OCCUPANCY. IT IS THE UNDERSTANDING OF THIS
 OFFICE THAT THIS ADDRESS WILL NO LONGER BE FUNCTIONING
 AS A MERCANTILE OCCUPANCY.
  
 THE AREA OF THE MEZZANINE IS PERMITTED TO BE ONE-HALF
 THE SIZE OF THE OPEN AREA OF THE FIRST FLOOR FOR
 MERCANTILE OCCUPANCIES ONLY. OTHER OCCUPANCIES, SUCH AS
 STORAGE, LIMIT THE AREA OF THE MEZZANINE TO ONE-THIRD
 THE OPEN AREA OF THE FIRST FLOOR. ENCLOSED SPACE
 (BATHROOM/OFFICE ETC.) SHALL NOT BE INCLUDED IN A
 DETERMINATION OF THE SIZE OF THE ROOM IN WHICH THE
 MEZZANINE IS LOCATED.
  
 STAIRS SHALL HAVE A MINIMUM TREAD DEPTH OF 11-INCHES.
  
 HANDRAILS ARE REQUIRED ON BOTH SIDES OF THE STAIR.
 HANDRAIL ENDS SHALL BE RETURNED TO THE WALL OR FLOOR OR
 SHALL TERMINATE AT NEWEL POSTS. HANDRAIL CROSS SECTION
 SHALL HAVE A DIAMETER OF NOT LESS THAN 1.25-INCHES AND
 NOT MORE THAN 2-INCHES. HANDRAIL SHALL PROVIDE A
 CLEARANCE OF NOT LESS THAN 1.5-INCHES BETWEEN THE
 HANDRAIL AND THE WALL WHICH IT IS FASTENED.
  
 GUARDS, AT LEAST 42-INCHES TALL, SHALL BE PROVIDED AT
 THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE,
 ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR. OPEN
 GUARDS SHALL PROHIBIT THE PASSAGE OF A 4-INCH DIAMETER
 SPHERE UP TO A HEIGHT OF 34-INCHES. THE TRIANGULAR
 OPENINGS FORMED BY THE RISER, TREAD AND BOTTOM ELEMENT
 OF THE GUARDRAIL SHALL PROHIBIT THE PASSAGE OF A 6-INCH
 DIAMETER SPHERE.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  
  