| Plan Review Notes For Permit 11120632 |
| Permit Number |
11120632 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-11 11:15:11 | 7426 SOUTH DIXIE HIGHWAY | | | PERMIT #11120632 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. | | | NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT | | | LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL | | | CONTRAST THE BACKGROUND. | | | | | | INDICATE THE OCCUPANCY TYPE AND OCCUPANT LOAD FOR THE | | | SPACE. | | | | | | FIRE EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF | | | 2A:10BC AND SHALL BE TAGGED BY A LICENSED FIRE | | | EXTINGUISHER COMPANY. | | | | | | DOORS SHALL BE ARRANGED TO BE OPENED READILY FROM THE | | | EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED. LOCKS, | | | IF PROVIDED, SHALL NOT REQUIRE THE USE OF A KEY, TOOL, | | | OR SPECIAL KNOWLEDGE OR EFFORT FOR OPERATION FROM THE | | | EGRESS SIDE. THUMB-TURN STYLE LOCK TO BE EQUIPPED WITH | | | A LOCKED/UNLOCKED INDICATOR. | | | | | | EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE | | | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING | | | FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS | | | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN | | | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 | | | FEET ON CENTER. | | | | | | PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY SHALL | | | BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. PROVIDE | | | DETAILS. | | | | | | PROVIDE FIRE DAMPERS FOR THE DUCTWORK PENETRATING FIRE | | | BARRIERS. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|