| 2012-01-06 08:52:19 | BUILDING PLAN REVIEW |
| | PERMIT: 11120625 |
| | ADD: 2119 S DIXIE HWY |
| | CONT: SOUTHEAST CONSTRUCTION |
| | TEL: (954)394-3991 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 01/06/2012 |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) 2007 FBC-B ADMINISTRATIVE CODE (WPB) 106.1.3 QUALITY |
| | OF PLANS. THESE ARE PHOTOCOPIED PLANS AND NOT OF |
| | SUFFECIENT CLARITY TO BE SCANNED INTO THE CITY'S RECORD |
| | RETENTION PROGRAM WITHOUT LOSS AND CLARITY. |
| | 106.1.1PROVIDE DRAFTSMAN QUALITY PLANS WITH SUFFICIENT |
| | CLARITY, DETAILS INDICATING THE LOCATION, SCOPE OF |
| | WORK, SHOW DETAILS THAT IT WILL CONFORM TO THE |
| | PROVISIONS OF THIS CODE AND REVELENT LAWS, ORDINANCES |
| | RULES & REGULATIONS, AS DETERMINED BY THE BUILDING |
| | OFFICIAL, PLEASE REVIEW 106.3.5 FOR THE MINIMUM PLAN |
| | REVIEW CRITERIA FOR BUILDING PLANS. |
| | |
| | 2) THE PLANS ARE LACKING A TITLE BLOCK INDICATING WHO |
| | THE DESIGNER IS FOR THIS PROJECT, 106.1 IF THE DESIGGN |
| | IS BY THE CONTRACTOR OF RECORD THEN THEEY MUST TAKE |
| | OWNERSHIP OF THE PROJECT WITH PRINTING THEIR NAME, |
| | SIGNING THEIR NAME AND APPLYING THEIR LICENSE NUMBER TO |
| | THE PLANS THEY HAVE DEVELOPED. |
| | |
| | 3) THE PROPERTY APPRAISERS OFFICE INDICATES THIS AREA |
| | TO HAVE BEEN CONSIDERED STORAGE WHICH WILL MEAN THIS IS |
| | A CHANGE OF OCCUPAANCY. THIS ENACTS THE 2007/09 FLORIDA |
| | EXISTING BUILDING CODE CHAPTER 9. EX BLDG CODE 901.3.1 |
| | PAARTIAL CHANGE OF OCCUPANCY CLASSIFICATION. WHERE A |
| | PORTION OF AN EXISTING BUILDING IS CHANGED TO A NEW |
| | OCCUPANCY CLASSIFICATION, SECTION 912 OF THE EX BLDG |
| | CODE SHALL APPLY. |
| | |
| | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| | RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| | THIS REVIEW. |
| | |
| | 3A) PLANS FAIL TO INDICATE MINIMUM BLDG TYPE |
| | |
| | 3B) PLANS FAIL TO PROVIDE SQ. FT OF THE BUILDING TYPE & |
| | THE MAIN USE (OCCUPANCY) FOR THE BUILDING OR IF MIXED |
| | USE. |
| | |
| | 3C) PLANS FAIL TO INDICATE IF THIS BUILDING CONTAINS A |
| | ACTIVE FIRE SPRINKLER SYSTEM. |
| | |
| | 3D) THE SECOND FLOOR AREA DOES NOT PROVIDE ENCLOSED |
| | STAIRWELLS, ALSO INDICATE FIRE RATING. |
| | |
| | 3E) PLANS FAIL TO PROVIDE VERTICAL ACCESSIBILITY, IF |
| | THE OLD FREIGHT ELEVATOR IS TO BE USED PLEASE INDICATE |
| | THE FIRE RATING AROUND SAID ELEVATOR AND 1 HOUR RATED |
| | FIRE DOORS. |
| | IT ALSO APPEARS THE OFFICE AREA TO THE RIGHT OF THIS |
| | NEW OFFICE AREA IS AT DIFFERENT FLOOR ELEVATIONS WILL |
| | THE USE OF A LULA LIFT BE USED FOR CODE COMPLIANCE IN |
| | THIS AREA? |
| | |
| | 3F) ACCESSIBILITY DUTY TO PROVIDE ACCESSIBILTY 20% |
| | DISPROPORTIONATE COST. 2007 FBC-B 11-4.1.6.(2)(2)(A). |
| | |
| | 3G) IF BUILDING IS NOT FIRE SPRINKLERED PLEASE SHOW |
| | COMPLIANCE WITH AREA OF RESCUE ASSISTANCE. |
| | |
| | 3H) PLEASE PROVIDE INFORMATION FOR ELECTRICAL, |
| | MECHANICAL, ENERGY CODE COMPLIANCE. |
| | |
| | 3I) PLANS INDICATE THE USE OF A STORE ROOM WHICH IS |
| | OVER 100 SQ FT, PLANS DO NOT SHOW SEPERATION BETWEEN |
| | THIS AREA AND OFFICE AREA NOR A RATED DOOR. |
| | |
| | 4) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | |
| | THIS LIST IS NOT COMPLETE, THERE ARE TO MANY UNKNOWN |
| | FACTORS TO DO A COMPLEETE REVIEW. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |