2012-01-17 12:32:03601 CLEARWATER PARK
 PERMIT #11120607
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER NFPA 72, SMOKE DETECTORS SHALL NOT BE INSTALLED IN
 UNSPRINKLERED ELEVATOR HOISTWAYS UNLESS THEY ARE
 INSTALLED TO ACTIVATE SMOKE RELIEF EQUIPMENT.
  
 THERE IS AN EXISTING FIRE SHUTTER (WITH FUSIBLE LINK?)
 ON THE FIRST FLOOR ADJACENT TO THE STAIR. PROVIDE SMOKE
 DETECTORS ON EACH SIDE OF THE SHUTTER TO ACTIVATE THE
 SHUTTER. FIRE SHUTTER SHALL ALSO DROP UPON ACTIVATION
 OF OTHER FIRE ALARM DEVICES.
  
 PER LOCAL CODE AMENDMENTS, DUCT SMOKE DETECTORS SHALL
 INITIATE A GENERAL FIRE ALARM CONDITION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW