2012-01-24 15:44:05RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS.
  
 1- NEED TO PROVIDE A 36" MINIMUM LANDING AT DOOR AS
 REQUIRED BY SEC. R311.4.3 OF THE 2007 FLORIDA
 RESIDENTIAL CODE. REVISE DRAWINGS AS REQUIRED. AND,
 CLEARLY SHOW NUMBER OF RISERS REQUIRED. DRAWING
 SUBMITTED SHOWS 21" HEIGHT FROM THE DOOR SILL TO THE
 FINISH GROUND, BUT ONLY TWO RISERS WERE SHOWN.
  
 2- PROVIDE COMPLETE STRUCTURAL FRAMING DETAIL FOR NEW
 DOOR. KEEP IN CONSIDERATION THAT EXISTING HOUSE
 CONSTRUCTION IS HOLLOW TILE. THE DOOR ANCHORING
 REQUIREMENTS NEED TO COMPLY WITH SEC. R613.6.
 STRUCTURAL FRAMING NEED TO COMPLY WITH THE DESIGN
 PRESSURES REQUIRED BY SEC. R301.2.1.4.3.
  
 3- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR THE NEW DOOR TO BE INSTALLED. DOOR
 NEEDS TO MEET THE DESIGN PRESSURES OF SEC.
 R301.2.1.4.3. NO PRODUCT APPROVAL WAS SUBMITTED. ONLY
 STORM SHUTTERS PRODUCT APPROVAL WAS SUBMITTED.
  
 4- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE
 INSTALLATION OF STORM PANELS.
 ***NOTE: HOUSE CONSTRUCTION IS HOLLOW TILE. VERIFY THAT
 STORM PANEL PRODUCT APRPOVAL INCLUDES THE INSTALLATION
 OF STORM SHUTTERS TO HOLLOW CLAY.
  