| Plan Review Notes For Permit 11120562 |
| Permit Number |
11120562 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-12-29 13:23:41 | BUILDING PLAN REVIEW | | | PERMIT: 11120562 | | | ADD: 1475 CENTREPARK BLVD # 130 | | | CONT: FISHER | | | TEL: (561)691-4716 | | | | | | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2007 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PLEASE REVIEW SHEET A-2 AND A-3 FOR DISCREPANCY IN | | | DOOR INDENTIFICATION. SHEET A3 DOOR MARK "B" IS | | | INDICATED AS A 20 MINUTE DOOR, FBC-B TABLE 715.4 | | | FOR EXIT ENCLOSURE AND EXIT PASSAGE WAYS A 1 HOUR RATED | | | WAL REQUIRES A 1 HOUR RATED DOOR, THE 450 DEGREE | | | TEMPERATURE RISE IS NOT REQUIRED FBC-B 715.4.4EXCEPTION | | | FOR FULLY SPRINKLERED BUILDINGS. THE SAME DOOR ON SHEET | | | A2 IS INDINTIFIED AS A TYPE "C" DOOR WHICH IS A BI-FOLD | | | IN THE DOOR SCHEDULE. | | | | | | 12/29/11 A CALL IS INTO THE DESIGN PROFESSIONAL ALLEN | | | BIRSE FOR RED LINING OF PLAN. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | 12/30 /11 | | | I SPOKE WITH DESIGNER ARCHITECT ALLEN BURSE AND OK TO | | | RED LINE PLANS IN REGARD TO DOOR LEADING INTO THE EXIT | | | PASSAGEWAY TABLE 715.4 1 HOUR/ FIRE SPRINKLERED | | | BUILDING. JW |
|