| 2012-02-15 09:37:42 | |
| | FBC 2007 PLUMBING REVIEW #1 |
| | DENIED: |
| | |
| | 1. NOT COMPLIED AT THIS TIME: |
| | THERE ARE NO PLUMBING FACILITIES FOR THE 2ND FLOOR |
| | WHICH IS MORE THAN ONE FLOOR LEVEL ABOVE THE BASEMENT. |
| | 403.4.1 LOCATION OF TOILET FACILITIES IN OCCUPANCIES |
| | OTHER THAN COVERED MALLS. IN OCCUPANCIES OTHER THAN |
| | COVERED MALLS, THE REQUIRED PUBLIC AND EMPLOYEE TOILET |
| | FACILITIES SHALL BE LOCATED NOT MORE THAN ONE STORY |
| | ABOVE OR BELOW THE SPACE REQUIRED TO BE PROVIDED WITH |
| | TOILET FACILITIES, AND THE PATH OF TRAVEL TO SUCH |
| | FACILITIES SHALL NOT EXCEED A DISTANCE OF 500 FEET (152 |
| | M). |
| | |
| | (IF THE RESTROOMS THAT ARE SHOWN ON THE EXITING PLAN - |
| | OPTION "B" ARE TO BE USED, PLEASE INCLUDE THE |
| | CALCULATIONS FOR THE OCCUPANT LOAD BASED ON THE SECOND |
| | FLOOR DINING AREA PLUS THE BUSINESS USE ON THAT FLOOR). |
| | |
| | 2. OK |
| | |
| | 3. BASEMENT LEVEL. SHEET A1.1 INDICATES |
| | NEW GANGED RESTROOM STALLS FOR BOTH THE MENS AND LADIES |
| | RESTROOMS. 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. THIS IS CONSIDERED NEW WORK AND THE |
| | ACCESSIBLE TOILET STALL FOR NEW CONSTRUCTION IS TO BE |
| | DESIGNED TO THE 2007/09 FBC-B 11-4 .17.3 & FIGURE 30E. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | 2007 /09 FBC-B 11-4.1.7.3 EXCEPTION FOR NEW |
| | CONSTRUCTION (1) : |
| | |
| | THE STANDARD ACCESSIBLE RESTROOM STALL SHALL CONTAIN AN |
| | ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF SUCH |
| | LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17 |
| | INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL |
| | MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO |
| | OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION |
| | 11-4.17 [SEE FIGURE 30(A) AND FIGURE 30(E)] ... |
| | |
| | (FIGURE 30E SHOWS A CLEAR FLOOR SPACE OF 60" WIDE WITH |
| | THE LAVATORY OUTSIDE OF THAT SPACE. THE NOTES FOR |
| | FIGURE 30E ALSO STATE THAT THERE ARE MANY POSSIBLE |
| | LOCATIONS FOR THE LAVATORY WITHIN THE TOILET STALL). |
| | |
| | 4. OK |
| | GAS IS NOT INCLUDED IN THIS REVIEW. SEPARATE PLANS, |
| | APPLICATION, AND REVIEWS ARE REQUIRED. |
| | |
| | 5. OK |
| | |
| | NEW NOTE: SOME METHOD OF KEEPING OIL OUT OF THE |
| | SANITARY SEWER WILL BE REQUIRED FOR THE ELEVATOR SUMP |
| | PUMP. THIS COULD BE ACCOMPLISHED WITH AN APPROVED OIL |
| | SENSING SUMP CONTROL SYSTEM. |
| | |
| | REVIEW BY |
| | LARRY WAGNER |
| | CHIEF PLUMBING INSPECTOR |
| | PHONE # 805-6692 |
| | EMAIL [email protected] |
| | FAX # 805-6676 |
| | |