| 2012-02-13 12:19:34 | BUILDING PLAN REVIEW |
| | PERMIT: 11120544 |
| | ADD: 200 CLEMATIS ST |
| | CONT: TBD |
| | TEL: (269)599-1341 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | FEB. 13/2012 |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1) 109.3.6.1 THE ENFORCING AGENCY SHALL REQUIRE A |
| | SPECIAL INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON |
| | A THRESHOLD BUILDING PURSUANT TO A STRUCTURAL |
| | INSPECTION PLAN PREPARED BY THE ENGINEER OF RECORD. THE |
| | STRUCTURAL INSPECTION PLAN MUST BE SUBMITTED TO THE |
| | ENFORCING AGENCY PRIOR TO THE ISSUANCE OF A BUILDING |
| | PERMIT FOR THE CONSTRUCTION OF A THRESHOLD BUILDING. |
| | THE PURPOSE OF THE STRUCTURAL INSPECTION PLAN IS TO |
| | PROVIDE SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO |
| | THAT THE BUILDING CAN BE ADEQUATELY INSPECTED FOR |
| | COMPLIANCE WITH THE PERMITTED DOCUMENTS. |
| | |
| | THRESHOLD INSPECTION PLAN FL S. S. 553.71(7) " |
| | THRESHOLD BUILDING" MEANING ANY BUILDING WHICH IS |
| | GREATER THAN (3) STORIES OR 50 FT IN HEIGHT, OR WHICH |
| | HAS AN ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN |
| | THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ FT IN AREA |
| | AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS. |
| | |
| | 2) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B. |
| | CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD |
| | BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S S |
| | 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS |
| | REQUIRED BY THIS CODE. |
| | CONTACT KEN CONRAD MANAGER OF THE SPECIAL INSPECTOR |
| | PROGRAM AT (561)805-6666 FOR FURTHER INFORMATION |
| | BEFORE THE PERMIT MAY BE ISSUED. |
| | |
| | A HOLD WILL BE PUT ON THIS PROJECT UNTIL THESE ITEMS |
| | ARE COMPLETED AS REQUESTED BY THE CHIEF BUILDING |
| | INSPECTOR KEN CONRAD: |
| | |
| | PLEASE CALL THE CITY OF WEST PALM BEACHS AUTOMATED |
| | TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR |
| | IN-PROGRESS INSPECTIONS FOR AUDITING OF JOBSITE |
| | INSPECTIONS. |
| | |
| | 2)(1) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR |
| | HISTORY FOR THIS TYPE OF CONCRETE RESTORATION. |
| | THIS MAY BE SUBMITTED TO KEN CONRAD BY E-MAIL. KEN |
| | CONRAD: [email protected] |
| | |
| | 2)(2) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A |
| | RESUME' OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. |
| | THE RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS |
| | SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE |
| | WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED, |
| | AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES |
| | WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST |
| | MEETING THE ABOVE CRITERIA. |
| | CONTACT KEN CONRAD |
| | TEL: 561-805-6666 |
| | E-MAIL: [email protected] |
| | |
| | 3) COMPLIED. THRESHOLD BLDG, REQUIRED STATEMENT: |
| | W.P.B. AMENDMENT 109.3.6.4.4 ALL PLANS FOR THE BUILDING |
| | WHICH ARE REQUIRED TO BE SIGNED AND SEALED BY THE |
| | ARCHITECT OR ENGINEER OF RECORD CONTAIN A STATEMENT |
| | THAT, TO THE BEST OF THE ARCHITECT'S PR ENGINEER'S |
| | KNOWLEDGE, THE PLANS AND SPECIFICATIONS COMPLY WITH THE |
| | APPLICABLE FIRE-SAFETY STANDARDS AS DETERMINED BY THE |
| | LOCAL AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633 |
| | FLORIDA STATUTE. |
| | |
| | 4) COMPLIED. 109.3.6 THRESHOLD BUILDINGS, OPERATING |
| | GUIDELINES FOR THRESHOLD INSPECTORS #26. ASSURE THAT |
| | THE DESIGNER HAS REQUIRED ON THE PLANS OR |
| | SPECIFICATIONS ONE MATERIAL, APPROVED FOR FIRE STOPPING |
| | PENETRATIONS, FOR WALLS AND CEILINGS. |
| | |
| | |
| | 5) COMPLIED. SHEET A1 THE BUILDING CODE ANYLSIS |
| | INDICATES THE WEST WALL BEING A 2 HR RATED WALL. THIS |
| | WALL SHOULD BE A 3 HOUR RATED WALL, 2007/09 FBC-B TABLE |
| | 601, TABLE 602, < THAN 5'-0" FROM THE PROPERTY LINE. |
| | |
| | 6) COMPLIED. |
| | |
| | 7) COMPLIED. BASEMENT LEVEL. SHEET A1.1 2HR RATED EXIT |
| | STAIR WITH A 1 HOUR RATED SHAFT WALL CONSTRUCTION UNDER |
| | THE STAIR, PLEASE PROVIDE A DETAIL AND WHAT WILL BE THE |
| | USE OF THIS NEW AREA? |
| | |
| | 8) COMPLIED. |
| | |
| | 9) COMPLIED. |
| | |
| | 10) 2ND REQUEST, BASEMENT LEVEL. SHEET A1.1 INDICATES |
| | NEW GANGED RESTROOM STALLS FOR BOTH THE MENS AND LADIES |
| | RESTROOMS. 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. THIS IS CONSIDERED NEW WORK AND THE |
| | ACCESSIBLE TOILET STALL FOR NEW CONSTRUCTION IS TO BE |
| | DESIGNED TO THE 2007/09 FBC-B 11-4 .17.3 & FIGURE 30E. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | 2007 /09 FBC-B 11-4.1.7.3 EXCEPTION FOR NEW |
| | CONSTRUCTION (1) STANDARD ACCESSIBLE RESTROOM STALLS |
| | SHALL CONTAIN AN ACCESSIBLE LAVATORY WITHIN IT. |
| | |
| | 11) COMPLIED. |
| | |
| | 12) SECOND REQUEST. SHEET A2, A5 & S-1 SHOW INFILL OF |
| | AN EXTERIOR BLOCK WALL. S1 ALSO INDICATES A CUT SECTION |
| | C/S3 NO SUCH DETAIL PROVIDING INFORMATION ON THE |
| | VERTICAL AND HORIZONTAL REINFORCEMENT FOR THE INFILL |
| | BLOCK. 106.1.2 ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 13) COMPLIED. |
| | |
| | 14)COMPLIED. |
| | |
| | 15) COMPLIED. |
| | |
| | 16)COMPLIED. |
| | |
| | 17) SEMI -COMPLIED. A6.1 & S-2 THE ELEVATOR DESIGN DOES |
| | NOT INDICATE WHAT TYPE OF SYSTEM IS TO DESIGNED AT THIS |
| | POINT, NOTE DIMINSION FOR SUMP SIZE NOT PROIDED, 3004.4 |
| | NOR DOES THE PLANS INDICATE COMPLIANCE WITH 3007.1 |
| | ELEVATOR ACCESSIBLITY REQUIREMENTS FOR THE PHYSICALLY |
| | HANDICAPPED. FBC-B 3007. IF NOT USING WHEEL CHAIR LIFT. |
| | 2ND REVIEW COMMENT- THE REQUIREMENT FOR THE SUMP IS |
| | LOCATED WITHIN THE BLDG CODE, THE SIZING OF THE SUMP |
| | PIT IS LOCATED WITH IN THE PLUMBING CODE REQUIRING A 18 |
| | INCH WIDE BY 24 INCH DEEP PIT. PLEASE BE AWARE THAT IF |
| | A HYDROLIC ELEVATOR IS INSTALLED, IF THERE IS A |
| | HYDROLIC LEAK IT MAY NOT GO TO SANITARY, PLEASE SEE |
| | PLUMBING COMMENTS. |
| | |
| | 18) COMPLIED. |
| | |
| | 19)COMPLIED. |
| | |
| | 20) COMPLIED. |
| | |
| | NEW COMMENTS |
| | |
| | 21) IN REGARDS TO THE 2ND FLOOR EXITING. 2007/09 EXIST |
| | BLDG CODE 601.2 ALLOWS FOR AN EXISTING BUILDING TO BE |
| | ALTERED OR PORTIONS THERE OF AND SHALL NOT BE ALTERED |
| | SUCH THAT THE BUILDING BECOMES LESS SAFE. PLEASE |
| | PROVIDE WHAT THTE OCCUPANT LOAD WOULD HAVE BEEN BEFORE |
| | THE REMOVAL OF THE 2ND STORY RESTROOMS. WITH THE |
| | RECONFIGURATION OF THE 2ND FLOOR IT WILL NEED TO BE |
| | EQUAL TO OR LESS THAN THE OCCUPANT LOAD FOR THE 2ND |
| | FLOOR BEFORE THE REMODELING TOOK PLACE.THE EXISTING |
| | BLDG CODE 705.3 NUMBER OF EXITS . THE NUMBER OF EXITS |
| | SHALL BE IN ACCORDANCE WITH THE APPROPRIATE SECTIONS OF |
| | THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | 22) THE NEW STAIRWWELL TO THE BASEMENT IS CONSIDERED |
| | NEW WORK AND WILL NEED TO MEET THE REQUIREMENTS FOR NEW |
| | CONSTRUCTION. 2007 EXISTING BUILDING CODE LEVEL II |
| | 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. 2007/09 |
| | FBC-B 1020.1 VERTICAL SHAFT ENCLOSURES. |
| | |
| | 23) OUTSWING KAWNEER STORE FRONT DOORS NOA 09-0129.01 |
| | GLAZING TYPE NOT PROVIDED TYPE A & B DO NOT MEET |
| | PRESSURES CLASS C & D DO MEET PRESSURERS? PLEASE |
| | PROVIDE ADDITIONAL INFORMATION AS TO WHICH GLAZING |
| | SYSTEM TO BE INSTALLED. |
| | |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |
| | |
| | |
| | |
| | |
| | |
| | |