| | FBC 2007 PLUMBING REVIEW #1 |
| | DENIED: |
| | |
| | 1. THERE ARE NO PLUMBING FACILITIES FOR THE 2ND FLOOR |
| | WHICH IS MORE THAN ONE FLOOR LEVEL ABOVE THE BASEMENT. |
| | 403.4.1 LOCATION OF TOILET FACILITIES IN OCCUPANCIES |
| | OTHER THAN COVERED MALLS. IN OCCUPANCIES OTHER THAN |
| | COVERED MALLS, THE REQUIRED PUBLIC AND EMPLOYEE TOILET |
| | FACILITIES SHALL BE LOCATED NOT MORE THAN ONE STORY |
| | ABOVE OR BELOW THE SPACE REQUIRED TO BE PROVIDED WITH |
| | TOILET FACILITIES, AND THE PATH OF TRAVEL TO SUCH |
| | FACILITIES SHALL NOT EXCEED A DISTANCE OF 500 FEET (152 |
| | M). |
| | |
| | 2. THE MENS ROOM IN THE BASEMENT LEVEL HAS MORE |
| | FIXTURES THAN THE WOMENS ROOM. WHILE THE RESTAURANT IS |
| | LICENSED UNDER F.S. 509, PLEASE SEE THE EXCEPTION FOR |
| | 403.1.1 POTTY PARITY. THE SAME NUMBER OF WATER CLOSETS |
| | IS REQUIRED FOR WOMEN AS THE COMBINED W.C AND URINALS |
| | FOR MEN: |
| | |
| | 403.1.1 POTTY PARITY. IN ASSEMBLY OCCUPANCIES, |
| | RESTROOMS WHICH ARE OPEN TO THE PUBLIC MUST HAVE A |
| | RATIO OF 3:2 WATER CLOSETS PROVIDED FOR WOMEN AS THE |
| | COMBINED TOTAL OF WATER CLOSETS AND URINALS PROVIDED |
| | FOR MEN, UNLESS THESE ARE TWO OR FEWER SUCH FIXTURES |
| | FOR MEN, IN ACCORDANCE WITH ?553.86, FLORIDA STATUTES. |
| | |
| | EXCEPTION: THIS SECTION DOES NOT APPLY TO |
| | ESTABLISHMENTS LICENSED UNDER CHAPTER 509, FLORIDA |
| | STATUTES, IF THE ESTABLISHMENT DOES NOT PROVIDE MEETING |
| | OR BANQUET ROOMS WHICH ACCOMMODATE MORE THAN 150 |
| | PEOPLE, AND THE ESTABLISHMENT HAS AT LEAST THE SAME |
| | NUMBER OF WATER CLOSETS FOR WOMEN AS THE COMBINED TOTAL |
| | OF WATER CLOSETS AND URINALS FOR MEN. |
| | |
| | 3. THE ADA STALLS WILL REQUIRE A LAV INSTALLED IN THE |
| | STALL PER 11-4.17 EXCEPTION (1) SEE FIGURE 30(E) |
| | |
| | 4. GAS IS NOT INCLUDED IN THIS REVIEW. SEPARATE PLANS, |
| | APPLICATION, AND REVIEWS ARE REQUIRED. |
| | |
| | 5. SHEET P5 - HOSE BIBBS REQUIRE SEPARATE SHUT OFF |
| | VALVES: |
| | 606.2 LOCATION OF SHUTOFF VALVES. |
| | 2. ON THE WATER SUPPLY PIPE TO EACH SILLCOCK IN OTHER |
| | THAN ONE- AND TWO-FAMILY RESIDENTIAL OCCUPANCIES. |
| | |
| | REVIEW BY |
| | LARRY WAGNER |
| | CHIEF PLUMBING INSPECTOR |