| Plan Review Notes For Permit 11120544 |
| Permit Number |
11120544 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-20 14:04:44 | PLANS DENIED | | | 1) SEPARATE APPLICATION PLANS AND PERMIT REQUIRED FOR | | | HOOD AND COOLERS. | | | 2) PROVIDE FRESH AIR CALCULATION'S ON THE PLANS. | | | 3) PROVIDE MANUFACTURERS INSTALLATION INSTRUCTIONS FOR | | | A/C EQUIPMENT WITH THE PLANS. | | | 4) PROVIDE PRODUCT APPROVALS FOR OUTDOOR LOUVERS. | | | 5) REFER TO SECTION 606.2.1 SUPLY AIR AND SECTION 606.3 | | | INSTALLATION. 2007 FBC (M) | | | 6) REFER TO SECTION 606.4.1 SUPERVISION.2007 FBC (M) | | | 7) REFER TO SECTION 607.5.1 FIRE WALLS 2007 FBC (M) . | | | REFERRING TO PAGE A1.1 | | | ROOM'S 001 AND 005 ON THE PLANS. | | | 8) REFER TO NOTE # 10 ON PAGE M-2 THIS IS A TYPE ONE | | | BUILDING CAN NOT USE PVC. | | | 9) PLEASE VERIFY THAT A/C UNIT # 6 IS IN STORAGE ROOM | | | IN BASEMENT. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | NOMAD 5055 @WPB.ORG |
|