| Plan Review Notes For Permit 11120530 |
| Permit Number |
11120530 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-12-28 08:00:48 | FBC 2007 PLUMBING REVIEW #1 | | | DENIED: | | | | | | 1. BY REMOVING A WATER CLOSET IN EACH RESTROOM THE | | | FIXTURE COUNT FOR THE FLOOR MAY BE LESS THAN REQUIRED. | | | PLEASE SHOW THE CALCULATIONS FOR THE REQUIRED FIXTURES. | | | FBC PLUMBING TABLE 403.1 - FOR BUSINESS OCCUPANCY FOUR | | | WC/ URINALS = 100 OCCUPANTS. | | | | | | 2. 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. | | | PLUMBING RISER DIAGRAM REQUIRED. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|