| 2012-01-19 09:17:15 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- AFTER PLANS ARE REVISED, PLEASE BRING THEM TO PALM |
| | BEACH COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES |
| | ARE DUE. THEN, BRING BACK STAMPED PLANS AND COPY OF |
| | PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 2- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | N1100.3 OF CHAPTER 13 FLORIDA RESIDENTIAL CODE. |
| | |
| | 3- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) WINDOWS AS SHOWN ON PLANS. |
| | |
| | B) EXTERIOR DOORS AS SHOWN ON PLANS. |
| | |
| | C) FLAT ROOF ASSEMBLY. AND, PLEASE SPECIFY WHICH |
| | APPROVED ASSEMBLY IS GOING TO BE INSTALLED. ALSO, |
| | PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT |
| | PERIMETER AND CORNER AREAS. NOTE: IF THE PRODUCT |
| | APPROVAL SUBMITTED REQUIRES SIGNED AND SEALED |
| | CALCULATIONS, THEN THOSE CALCULATIONS NEED TO BE SIGNED |
| | AND SEALED. |
| | |
| | D) HURRICANE SHUTTERS IF THE DOORS AND WINDOWS PRODUCT |
| | APPROVALS SUBMITTED DON'T HAVE IMPACT GLASS. AND, |
| | PROVIDE A COMPLETE SHUTTERS INSTALLATION SCHEDULE. |
| | |
| | E) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND DETAILS. |
| | |
| | 4- PROVIDE COMPLETE ROOF FRAMING PLAN. SHOW ALL FRAMING |
| | MEMBERS SIZES AND CONNECTORS. SPECIFY ATTACHMENT TO |
| | EXISTING ROOF. SPECIFY ROOF SLOPE. ETC. SEC. 106.1.1 |
| | CITY AMENDMENTS TO FBC. |
| | |
| | 5- SPECIFY THE CALCULATED DESIGN PRESSURES FOR THE |
| | EXTERIOR DOORS AND WINDOWS AS REQUIRED BY SEC. |
| | R301.2.1.4.3 FLORIDA RESIDENTIAL CODE. |
| | |
| | 6- SPECIFY EGRESS FROM THE EXISTING BEDROOM AS REQUIRED |
| | BY SEC. R310. |
| | |
| | 7- SPECIFY SMOKE ALARMS AS REQUIRED BY SEC. R313. |
| | |
| | 8- PROVIDE STRUCTURAL BUCK DETAILS FOR EXTERIOR DOORS |
| | AND WINDOWS AS REQUIRED BY SEC. R613.6. |
| | |
| | 9- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. UPDATE THE VALUE TO INCLUDE ALL MATERIALS, LABOR |
| | AND DESIGN PROFESSIONAL FEES AS REQUIRED BY SEC. 108.3 |
| | CITY AMENDMENTS. |
| | |
| | 10- SHEET 1 OF 3 SUBMITTED: |
| | A) INFORMATION ON FLOOR PLAN SUBMITTED IS NOT CLEAR. |
| | (1) STEEL REINFORCING SPECIFICATIONS FOR CORNER COLUMNS |
| | ARE NOT CLEAR AND DON'T MATCH INFORMATION SHOWN ON THE |
| | FLOOR PLAN. (2) WHAT'S "NEW FRAME WALL LEADING TO BACK |
| | OF HOUSE" NOTE MEANS. IS THIS FRAME ADDITION OR |
| | CONCRETE BLOCK?. COORDINATE WITH WALL SECTION ON SHEET |
| | 3 OF 3. (3) INFORMATION FOR NEW HALLWAY AND EXISTING |
| | UTILITY IS NOT CLEAR. DRAWING DON'T SHOW THE WALLS AND |
| | FRAMING AROUND DOORS IS NOT CLEAR. (4) SPECIFY VERTICAL |
| | REINFORCEMENT AT THE ENDS OF DOORS AND WINDOWS |
| | OPENINGS. |
| | |
| | B) REVISE GENERAL NOTES. (1) THERE IS NOT SBC. REFER TO |
| | THE 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | (2) THERE IS NOT TABLE 1606.28. SEE 2007 FLORIDA |
| | RESIDENTIAL L CODE AND SPECIFY ALL THE DESIGN LOADS AS |
| | REQUIRED BY SEC. R301 AND TABLE R301.5. SPECIFY ALL THE |
| | LIVE AND DEAD LOADS, BUILDING EXPOSURE AND THE WIND |
| | SPEED. |
| | |
| | C) SPECIFY SIZE OF EXTERIOR DOORS AND WINDOWS TO VERIFY |
| | COMPLIANCE WITH THE DESIGN PRESSRUES OS SEC. |
| | R301.2.1.4.3. |
| | |
| | 11- SHEET 3 OF 3: |
| | A) REVISE WALL SECTIONS: (1) SPECIFY ALL STRUCTURAL |
| | CONNECTORS. SEC. 106.1.2 CITY AMENDMENTS. (2) PROVIDE |
| | ENGINEERING SHOWING REINFORCING FOR THE EXISTING ROOF |
| | TRUSSES TO BE CUT. SEC. 106.1.2 CITY AMENDMENTS. (3) |
| | COORDINATE VERTICAL REINFORCEMENT SHOWN ON THE TYPICAL |
| | WALL SECTION WITH REVISED INFORMATION ON PLANS. |
| | COORDINATE WITH ITEM #10(A) ABOVE. |
| | |
| | B) CLARIFY PLYWOOD NAILING NOTES. ARE THESE NOTES FOR |
| | ROOF SHEATHING OR WALL SHEATHING. ROOF SHEATHING |
| | REQUIRES MIN. 8D RING SHANK NAILS. SEE SEC. R803.2.3.1. |
| | AND ROOF ZONE #3 REQUIRES NAIL SPACING AT 4"O.C. |
| | |
| | C) REVISE SPECIFICATIONS FOR EXISTING ROOF TILE. 30# |
| | UNDERLAYMENT ALONE DOESN'T COMPLY WITH SEC. R905.3.3. |
| | ALSO, CLARIFY IF PERMIT INCLUDES RE-ROOFING EXISTING |
| | HOUSE. |
| | |