2011-12-29 11:44:23BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES
 IN THIS PLAN PRIOR TO INSPECTION WILL RESULT IN FAILED
 INSPECTION(S) AND THE ASSESSMENT OF
 RE-INSPECTION FEE(S). REVISIONS REQUIRE ADDITIONAL
 REVIEWS WITH ASSOCIATED FEES.
  
 1) PROVIDE FIRE STOP SYSTEM AT TIME OF FRAMING
 INSPECTION.
 FBC-B 712.3.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM.
 THROUGH PENETRATIONS SHALL BE
 PROTECTED BY AN APPROVED PENETRATION FIRESTOP SYSTEM
 INSTALLED AS TESTED IN ACCORDANCE
 WITH ASTM E 814 OR UL 1479, WITH A MINIMUM POSITIVE
 PRESSURE DIFFERENTIAL OF 0.01 INCH
 (2.49 PA) OF WATER AND SHALL HAVE AN F RATING OF NOT
 LESS THAN THE REQUIRED FIRE-RESISTANCE
 RATING OF THE WALL PENETRATED.
  
 2) FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR
 ANY OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS
 SHALL BE EFFECTIVELY AND PERMANENTLY
 IDENTIFIED WITH SIGNS OR STENCILING IN A MANNER
 ACCEPTABLE TO THE AUTHORITY HAVING JURISDICTION.
 SUCH IDENTIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING AND IN CONCEALED SPACES. SUGGESTED
 WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE AND SMOKE
 BARRIER - PROTECT ALL OPENINGS."
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]