| Plan Review Notes For Permit 11120496 |
| Permit Number |
11120496 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-01-24 09:00:20 | | | | THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO | | | CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO | | | INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE | | | ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE | | | ADDITIONAL REVIEWS WITH ASSOCIATED FEES. | | | | | | 1) SHEET A.100 STRIKE DOOR#45 AND STORAGE CLOSET. LOBBY | | | AREA IS CONSIDERED PART OF THE VERTICAL EXIT AND ONLY | | | PENETRATIONS THAT PERTAIN TO THE EXIT ENCLOSURE ARE | | | PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT | | | AND DUCTWORK NECESSARY FOR INDEPENDENT PRESSURIZATION, | | | SPRINKLER PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR | | | FIRE DEPARTMENT COMMUNICATION SYSTEMS AND ELECTRICAL | | | RACEWAY SERVING THE EXIT ENCLOSURE AND TERMINATING AT A | | | STEEL BOX NOT EXCEEDING 16 SQUARE INCHES (0.010 M2). | | | | | | 2) SHEET A.100 NOTE #24 I SPOKE WITH THE JOBSITE | | | SUPERINTENDANT, THE NEW STOREFRONT GLAZING SYSTEM AND | | | ALL EXTERIOR GLAZING ARE BEING REPLACED, A REVISION | | | WILL BE REQUIRED WITH THE PRODUCT APPROVALS REVIEWED BY | | | THE DESIGNER OF RECORD AND SHOP DRAWINGS FOR THE NEW | | | INSTALATION. ADDITIONAL FEES WILL BE ASSESSED FOR NEW | | | SCOPE WORK,SEPARATE REVIEW AND ASSOCIATED FEES WILL | | | OCCUR. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] |
|