 1) SHEET A.100 STRIKE DOOR#45 AND STORAGE CLOSET. LOBBY
 AREA IS CONSIDERED PART OF THE VERTICAL EXIT AND ONLY
 PENETRATIONS THAT PERTAIN TO THE EXIT ENCLOSURE ARE
 PROHIBITED EXCEPT FOR REQUIRED EXIT DOORS, EQUIPMENT
 AND DUCTWORK NECESSARY FOR INDEPENDENT PRESSURIZATION,
 SPRINKLER PIPING, STANDPIPES, ELECTRICAL RACEWAY FOR
 FIRE DEPARTMENT COMMUNICATION SYSTEMS AND ELECTRICAL
 RACEWAY SERVING THE EXIT ENCLOSURE AND TERMINATING AT A
 STEEL BOX NOT EXCEEDING 16 SQUARE INCHES (0.010 M2).
  
 2) SHEET A.100 NOTE #24 I SPOKE WITH THE JOBSITE
 SUPERINTENDANT, THE NEW STOREFRONT GLAZING SYSTEM AND
 ALL EXTERIOR GLAZING ARE BEING REPLACED, A REVISION
 WILL BE REQUIRED WITH THE PRODUCT APPROVALS REVIEWED BY
 THE DESIGNER OF RECORD AND SHOP DRAWINGS FOR THE NEW
 INSTALATION. ADDITIONAL FEES WILL BE ASSESSED FOR NEW
 SCOPE WORK,SEPARATE REVIEW AND ASSOCIATED FEES WILL
 OCCUR.
  