Plan Review Notes
Plan Review Notes For Permit 11120496
Permit Number 11120496
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2012-01-05 12:05:17601 CLEARWATER PARK
 TRACKING #11120496
 MASTER #11100408
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET D.001 INDICATES A HANDRAIL TO BE 2-1/2". HANDRAIL
 DIAMETER SHALL NOT EXCEED 2-INCHES.
  
 AREA BELOW THE FRONT EXIT STAIR SHALL NOT BE USED FOR
 STORAGE.
  
 ONLY EQUIPMENT (LIGHTING, FIRE ALARM DEVICES, HVAC)
 ESSENTIAL TO THE FUNCTION OF THE STAIR IS PERMITTED IN
 THE STAIR. CHAIRS, SECURITY EQUIPMENT, CASEWORK,
 MAILBOXES, TELEVISIONS ETC. ARE NOT PERMITTED. INTEIOR
 WALL AND CEILING FINISH MATERIALS SHALL BE CLASS A OR B
 IN EXITS.
  
 DOOR #41 DOES NOT INDICATE THE FIRE RATING. FIRE DOOR
 SHALL NOT BE EQUIPPED WITH HOLD OPEN ARM.
  
 DOOR #6 NEEDS TO SWING IN THE DIRECTION OF EGRESS
 TRAVEL.
  
 MAGNETIC LOCKS ON INTERIOR DOORS #39, #40 AND #41 SHALL
 NOT BE UTILIZED AS ACCESS CONTROLLED EGRESS MAY EFFECT
 FREE EGRESS TO A SECONDARY EXIT. ALSO, THIS EQUIPMENT
 IS NOT ESSENTIAL TO THE FUNCTION OF THE EXIT STAIR.
  
 SEPARATE PLANS AND PERMIT NEEDED FOR FRONT ENTRY ACCESS
 CONTROLLED EGRESS SYSTEM.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  
  