| Plan Review Notes For Permit 11120496 |
| Permit Number |
11120496 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-05 12:05:17 | 601 CLEARWATER PARK | | | TRACKING #11120496 | | | MASTER #11100408 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SHEET D.001 INDICATES A HANDRAIL TO BE 2-1/2". HANDRAIL | | | DIAMETER SHALL NOT EXCEED 2-INCHES. | | | | | | AREA BELOW THE FRONT EXIT STAIR SHALL NOT BE USED FOR | | | STORAGE. | | | | | | ONLY EQUIPMENT (LIGHTING, FIRE ALARM DEVICES, HVAC) | | | ESSENTIAL TO THE FUNCTION OF THE STAIR IS PERMITTED IN | | | THE STAIR. CHAIRS, SECURITY EQUIPMENT, CASEWORK, | | | MAILBOXES, TELEVISIONS ETC. ARE NOT PERMITTED. INTEIOR | | | WALL AND CEILING FINISH MATERIALS SHALL BE CLASS A OR B | | | IN EXITS. | | | | | | DOOR #41 DOES NOT INDICATE THE FIRE RATING. FIRE DOOR | | | SHALL NOT BE EQUIPPED WITH HOLD OPEN ARM. | | | | | | DOOR #6 NEEDS TO SWING IN THE DIRECTION OF EGRESS | | | TRAVEL. | | | | | | MAGNETIC LOCKS ON INTERIOR DOORS #39, #40 AND #41 SHALL | | | NOT BE UTILIZED AS ACCESS CONTROLLED EGRESS MAY EFFECT | | | FREE EGRESS TO A SECONDARY EXIT. ALSO, THIS EQUIPMENT | | | IS NOT ESSENTIAL TO THE FUNCTION OF THE EXIT STAIR. | | | | | | SEPARATE PLANS AND PERMIT NEEDED FOR FRONT ENTRY ACCESS | | | CONTROLLED EGRESS SYSTEM. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | | | | |
|