2012-01-04 17:04:54RELOCATED PANEL IN FAMILY ROOM NEEDS TO BE ADDED TO THE
 ELECTRICAL RISER PLAN. INCLUDE THE PANEL SIZE, AND
 WIRING METHOD. UPDATE THE LOAD CALCULATION IF NEEDED.
 ALL MAIN ELECTRIC DISCONNECTS MUST BE GROUPED IN ONE
 LOCATION. ADD THE SUB PANEL TO THE PANEL SCHEDULE IF
 APPROPRIATE. NEC 215.5, 230.72
  
 ADD A RECEPTACLE AT THE BAR KITCHEN COUNTER TO SERVE
 THE FAMILY ROOM. NEC 210.52
  
 AN INTER SYSTEM BONDING STRIP IS REQUIRED AT THE
 SERVICE. NEC 250.94
  
 SECOND FLOOR MASTER BEDROOM REQUIRES A CARBON MONOXIDE
 DETECTOR.
  
  
 ROBERT LECKY
 COMMERCIAL COMBINATION PLANS EXAMINER
 [email protected]
 561-805-6718
  