| Plan Review Notes For Permit 11120485 |
| Permit Number |
11120485 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-04 17:04:54 | RELOCATED PANEL IN FAMILY ROOM NEEDS TO BE ADDED TO THE | | | ELECTRICAL RISER PLAN. INCLUDE THE PANEL SIZE, AND | | | WIRING METHOD. UPDATE THE LOAD CALCULATION IF NEEDED. | | | ALL MAIN ELECTRIC DISCONNECTS MUST BE GROUPED IN ONE | | | LOCATION. ADD THE SUB PANEL TO THE PANEL SCHEDULE IF | | | APPROPRIATE. NEC 215.5, 230.72 | | | | | | ADD A RECEPTACLE AT THE BAR KITCHEN COUNTER TO SERVE | | | THE FAMILY ROOM. NEC 210.52 | | | | | | AN INTER SYSTEM BONDING STRIP IS REQUIRED AT THE | | | SERVICE. NEC 250.94 | | | | | | SECOND FLOOR MASTER BEDROOM REQUIRES A CARBON MONOXIDE | | | DETECTOR. | | | | | | | | | ROBERT LECKY | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|