| Plan Review Notes For Permit 11120485 |
| Permit Number |
11120485 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-01-18 14:34:43 | REVISION, BUILDING REVIEW COMMENTS. | | | | | | 1- PRODUCT APPROVALS SUBMITTED FOR SINGLE HUNG WINDOWS, | | | FIXED WINDOWS AND HORIZONTAL SLIDER WINDOWS DON'T MEET | | | THE DESIGN PRESSURES CALCULATED BY THE ENGINEER OF | | | RECORD. NEED TO PROVIDE PRODUCT APPROVALS THAT MEET THE | | | CALCULATED DESIGN PRESSURES REQUIRED BY SEC. R301.2.4.3 | | | OF 2007 FLORIDA RESIDENTIAL CODE. | | | | | | 2- DRAWINGS SUBMITTED FOR FIXED WINDOW ARE FOR | | | NON-IMPACT WINDOWS. NEED TO PROVIDE IMPACT WINDOWS OR | | | OPENING PROTECTION AS REQUIRED BY SEC. R301.2.1.2. | | | | | | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS PRIOR | | | TO SUBMITTAL TO THIS OFFICE. SEC. 106.3.3 CITY | | | AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|